Technical Data; Equipment Ratings Table; Cable Lengths - Siemens 6SE2101–1AA01 Operating Manual

6se21 series simovert p
Table of Contents

Advertisement

Available languages

Available languages

2. TECHNICAL DATA

Rated supply voltage:
** – May be any number
Output voltage
Output frequency
Efficiency
Motor Power Factor
Ambient temperature (operation)
(unit must not be exposed to direct sunlight)
Storage/transport temperature
Degree of protection
Humidity
Frequency stability at ∆
referred to f
max
Frequency resolution
Overload rating

2.1 Equipment Ratings Table

Model No.
6SE2101–1AA01
6SE2102–1AA01
6SE2103–1AA01
6SE2103–3AA01
6SE2105–3AA01
6SE2108–3AA01
6SE2113–3AA01
6SE2117–3AA01
6SE2122–3AA01
6SE2127–3AA01
6SE2133–3AA01
6SE2142–3AA01
1
Siemens 4–pole motor, 1LA5 Series or equivalent
2
n
/n
n
= Current rating at 342 – 440 V
1
2
1
n
= Current rating at 440 – 550 V
2
3
Do not use semiconductor protection fuses

2.2 Cable Lengths

The inverters will operate satisfactorily with unscreened cables of up to 100 m (330 ft) in length and screened
or armoured cable of up to 10 m (33 ft) in length. For applications where longer cables are required, inductors
must be fitted to reduce capacitive currents. The following chokes are suitable for most applications:
Model No.
6SE210*–1AA01
6SE210*–3AA01
6SE211*/6SE212*–3AA01
6SE213*/6SE214*–3AA01
Models 6SE21**–1AA01
Models 6SE21**–3AA01 V
o
T
10
C
max
Input Voltage Range
198–264 V 1 Phase
198–264 V 1 Phase
198–264 V 1 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
342–550 V 3 Phase
Choke Type
4EP3601–3DB
4EP3601–8DB
4EP3800–4DB
4EP4000–4DB
2/1
V
1AC 50/60 Hz +/–1% 220 – 240 V +/–10%
3AC 50/60 Hz +/–1% 380 – 500 V +/–10%
V
0 – Rated supply voltage
Hz
0.0 – 400
> _ 0.94
< _ 0.9 lagging/inductive
o
0 – 40
C
o
C
–30 to +85
IP21 (NEMA 1)
o
0 – 95% at 25
C
Analogue set–point 1%
Digital set–point 0.01%
Hz
0.1
1.5 x rated current for up to 60 seconds
Max.
Dist. Fuse/
Input
Circuit
Current
Breaker
7 A
10 A
11 A
16 A
18 A
20 A
4 A
6 A
8 A
10 A
12 A
16 A
23 A
25 A
30 A
32 A
34 A
40 A
40 A
50 A
54 A
63 A
71 A
80 A
Inductance
3 x 1.4 mH
3 x 1.8 mH
3 x 0.7 mH
3 x 0.45 mH
English
Typical
Max.
Motor
Output
Rating
3
Current
hp
kW
2.8 A
0.75
0.55
0.75
3.9 A
1
6.8 A
2
1.5
4.0 A
2
1.5
7.6 A
5
3.0
2
12/11 A
7.5
5.5
19 A
10
7.5
25 A
15
11
32 A
20
15
2
38/34 A
25
18.5
46 A
30
22
2
60/52 A
40
30
1

Hide quick links: