Parameter
Description
Number
P11
DC Injection Braking
P12
Jog
P13∗
Slip Compensation
P14∗
Display Status / Analogue Output
P15
Voltage to Frequency
Relationship:
'knee point'
P16
Voltage to Frequency
Relationship:
curve type
P17∗
Current Limit
5/9
Display
Setting
Notes
(Factory
Setting)
Sets the dc injection voltage as a percentage of
00.0 –
the mains voltage. The optimum setting is
20.0%
dependent on motor type and inertia. Too high a
level will result in overcurrent and tripping of the
drive (F00). Too low a level will result in longer
than necessary stopping times. DC injection
braking is enabled automatically when P11 is
set to a non–zero value.
(00.0)
Sets the inverter frequency reached when the
00.1 –
400 Hz
jog control input is active. Overrides the
minimum frequency setting.
(05.0)
Sets the amount of slip compensation (Hz) added
00.0 –
to the output frequency when a current equal to
20.0 Hz
the current limit (set via P17) is supplying the
motor.
Note that excessive slip compensation will cause
the motor to increase speed above that
equivalent to the original set output frequency
and overloading may result.
i.e.
f
= f
+ (P13 x measured load current/P17)
output
set
(00.0)
Display
000
Output frequency
001
Output frequency X11.11 indicates current
Output current
002
Output current
003
(Except during parameterisation or fault
conditions.)
(000)
Sets the knee frequency on a user–defined
00.1 –
curve. Used when P06 is set to 006.
400 Hz
(50.0)
[60.0]
Linear from 0 Hz to knee frequency when P06
000
is set to 006.
Voltage proportional to (frequency)
001
P06 is set to 006.
(000)
This parameter sets the current limit of the
00.1 –
inverter in amperes. This current limit operates
inverter
after 60 s (P18 sets the overload limit) by
rated
reducing the output frequency until the output
output in
current falls below the set value. The decimal
Amperes
point display flashes when the current set by
P17 is exceeded or when the current limit is
(1.1 x
active.
inverter
rating)
English
Analogue Output
X11.11 indicates frequency
X11.11 indicates frequency
X11.11 indicates current
1.5
when