FRAME
PRESSURE
SIZE
PSIG (KPA)
150/300
1
(1034/2068)
150/300
2
(1034/2068)
150/300
3
(1034/2068)
150/300
4
(1034/2068)
150/300
5
(1034/2068)
150/300
6
(1034/2068)
150
(1034)
7
300
(2068)
150
(1034)
8
300
(2068)
Table 9 — 19XR Waterbox Nozzle Sizes
NOMINAL PIPE SIZE (IN.)
PASS
COOLER
1
8
2
6
3
6
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
10
3
8
1
14
2
12
3
10
1
14
2
12
3
10
1
14
2
14
3
12
1
14
2
14
3
12
38
ACTUAL PIPE ID (IN.)
CONDENSER
COOLER
8
7.981
6
6.065
6
6.065
10
10.020
8
7.981
6
6.065
10
10.020
8
7.981
6
6.065
10
10.020
8
7.981
6
6.065
10
10.020
10
7.981
8
6.065
10
10.020
10
10.020
8
7.981
14
13.250
12
12.000
12
10.020
14
12.500
12
11.376
12
9.750
14
13.250
14
13.250
12
12.000
14
12.500
14
12.500
12
11.376
CONDENSER
7.981
6.065
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
10.020
7.981
10.020
10.020
7.981
13.250
12.000
12.000
12.500
11.750
11.750
13.250
13.250
12.000
12.500
12.500
11.376

Advertisement