Page 1
Transport Air Conditioning OPERATION AND SERVICE MODELS AC310 & AC350 Rooftop Air Conditioning Units With BT324 Carrier Sutrak Digital Display (CSDD) 280P/282P Electronic Thermostat T--304 Rev A Change 07/09...
OPERATION AND SERVICE MANUAL TRANSPORT AIR CONDITIONING UNIT MODELS AC310 & AC350 ROOFTOP AIR CONDITIONING UNITS *CSDD - - BT324 (*Carrier Sutrak Digital Display) Electronic Thermostat - - 280P & 282P...
SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices.
Page 8
The Filter-drier May Contain Liquid Refrigerant. Slowly Loosen The Connecting Nuts And Avoid Contact With Exposed Skin Or Eyes. CAUTION The AC310 & AC350 Rooftop Systems have R134a service port couplings installed on the compres- sor and 1/4 inch flare (Acme) fittings installed on the unit piping. CAUTION To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to suction pressure before disconnecting.
Manual (280P) 77--62032--05 12 VDC BT324 *77--62032--06 12 VDC BT324 (Tropic) *NOTE: 77--62032--06 (Tropic) -- Has an AC310 Evaporator Section & an AC350 Condenser Section. Table 1- -2 AC 350 Models Part Number Voltage Controller With Heat Dual Loop Single Loop...
AC310 AC350 Evaporator Section Condenser Section Figure 1- -1 AC310/350 Rooftop Units 1.2.2 Condensing Section than refrigerant circulating inside the tubes; this results in condensation of the refrigerant into a liquid. The The dual (See Figure 1--2) and single loop (See...
Page 11
Condenser Fan and Motor Assembly Service Valve (High Side) Condenser Motor Support Filter Drier Upper Support Discharge Line Check Valve (Location) Filter Drier Figure 1- -2 Condensing Section Components (AC310 - - Dual Loop - - GEN I) T--304 04/08 1--3...
(to add in--dash service port), and condensate drain connections. The dual loop AC310 & AC350 (GEN I) evaporator The liquid line solenoid valve closes when the system is section (See Figure 1--4) includes the evaporator coils,...
Page 13
Dual Loop Evaporator Coil Assembly Sight Glass Heater Coil Heating Line Expansion Valve Access Port Evaporator Blower Assembly Liquid Line Solenoid Evaporator Motor Figure 1- -4 Evaporator Section Components (AC310 - -Dual Loop - - GEN I) T--304 04/08 1--5...
Single Loop Compressors 05G & 05K The drivers evaporator assembly is normally installed in The 05G (AC350) & 05K (AC310) compressor the vehicle dash area and interfaces with the rooftop unit assemblies used with the single loop units, includes the electrical cabeling and refrigerant piping.
AC310 - - Single Loop TM- -31 Compressor nents 12 Pounds (5.4 kg) without In--Dash unit AC310 - - Single Loop 05G or 05K Compressor The system is operated by an electronic thermostat type 13.2 to 15.4 Pounds (6.0 to 7.0 kg) without controller and/or manually operated switches.
& some TM31’s, the pressure switches are not Heating circuit (See Figure 1--7) components furnished located on the compressors. They are installed by Carrier Transport Air Conditioning include the heater cores and solenoid operated heat valves. Components in--line. furnished by the bus manufacturer may include a water temperature switch (WTS) and boost water pump.
Driver’s Evaporator Thermal Expansion Valve Subcooler Liquid Line Sight Glass Compressor (TM--21 or A--6) Service Port Service Valve Liquid Line Solenoid Condenser Coil Evaporator Coil Filter--Drier Heat Coil Receiver Note: Items 1 through 12 are typical, both systems. Figure 1- -6 Refrigerant Flow Diagram - - Cooling (Dual Loop) T--304 04/08 1--9...
Page 18
SUPPLY RETURN Heat Coil Heat Solenoid Valve Vehicle Radiator Optional Hand Valve Boost Pump Figure 1- -7 Flow Diagram - - Heating NOTE: In order to ensure water is entering the heater coils sufficiently heated, it is suggested that the OEM supplied Water Temperature Switch (WTS) close on temperature rise at 150°F (65.5°C). T--304 04/08 1--10...
Discharge Liquid Relief Valve Suction Coolant CONDENSER Discharge Check Valve Dash Air Suction Line Dash Air Liquid Line EVAPORATOR Figure 1- -8 Refrigerant Flow Diagram, Cooling (Single Loop) AC350 Thermal Expansion Valve Compressor Liquid Line Sight Glass Service Valve Service Port R134a Condenser Coil Service Port 1/4 Flare (Acme) 10.
If the engine is not running, start the engine. b. Actual start sequence depends on the operating co- The control switches supplied by Carrier Transport Air trol supplied. If only an ON/OFF switch is supplied, Conditioning will be marked with international symbols place the switch in the ON (fan symbol) position to (See Figure 2.1).
(High Ambient) 3.6°F. from the set point. The compressor clutch is disengaged at this time. 2.3.7 Override Mode - - AC310 (Dehumidification) 2.3.6 Compressor Unloader Control (Only with When in the heat mode the compressor will not operate. 05G or 05K Compressors) The thermostat will allow only COOL, VENT or HEAT modes independently.
2.3.8 Evaporator Fan Speed Selection 4. Through line U3, to energize the condenser fan re- lays (K14M & K15M). Energizing these relays will Evaporator fan speed(s) selection is one method of send B+ power to start the condenser fan motors. controlling the cooling and heating throughout the bus The unit is now in low speed cooling.
(See Figure 3--1). A 150 Amp @12 VDC or a125 Amp @ 24 VDC fuse in The BT324 Carrier Sutrak Digital Display (CSDD) is the battery compartment passes power for the clutch, marked with international symbols (See Figure 3--2).
Figure 3- -2 BT324 CSDD Controller KEYS LEDS Plus Key Display Minus Key Fresh Air Operation (Green) Recirculate/Fresh Air Key Manual Blower Control ’ON’ (Green) Blower Control Key Heating Mode (Green) Automatic Climate Control (A/C) Malfunction Light (Red) 3.3 SEQUENCE OF OPERATION BT324 CSDD NOTE The following blower steps are disabled when 3.3.1 Function of Keys when “Engine On”...
However, the blowers may be switched to manual mode A sensor malfunction is displayed by “i - -- -” or “o - -- -”. of operation by pressing the blower key. 3.5 CHANGING BETWEEN °F (FAHRENHEIT) Press the Plus or Minus keys to define one of 5 different AND °C (CELCIUS ) blower steps.
SECTION 4 TROUBLESHOOTING Table 4- -1 General System Troubleshooting Procedures INDICATION - - REFERENCE POSSIBLE CAUSES TROUBLE SECTION System Will Not Cool Compressor will not run Drive--Belt loose or defective Check Clutch coil defective Check/Replace Clutch malfunction Check/Replace Compressor malfunction See Table 1--3 Electrical malfunction Coach power source defective...
Table 4- -1 General System Troubleshooting Procedures - - Continued INDICATION - - REFERENCE POSSIBLE CAUSES TROUBLE SECTION Abnormal Noise Or Vibrations - - Continued Condenser or evaporator fans Loose mounting hardware Check/Tighten Defective bearings Replace Blade interference Check Blade missing or broken Check/Replace No Evaporator Air Flow Or Restricted Air Flow Air flow through coil blocked...
To avoid damage to the earth’s ozone layer, use a refrigerant recovery system whenever removing refriger- ant. The refrigerant recovery system is available from Carrier Transicold (Carrier Transicold P/N MVSII--115 or MVSII--240). When working with refrigerants you must comply with all local goverment environmental laws.
SUCTION CAUTION PRESSURE PRESSURE GAUGE GAUGE The AC310 & AC350 Rooftop Systems have R134a service port couplings installed on the compressor and 1/4 inch flare (Acme) fittings installed on the unit piping. CLOSED OPENED 5.4.1 Installing R- -134a Manifold Gauge/Hose SET...
5.5 PUMPING THE SYSTEM DOWN OR REMOV- ING THE REFRIGERANT CHARGE NOTE To avoid damage to the earth’s ozone layer, use a refrigerant recovery system whenever remov- ing refrigerant. 5.5.1 System Pump Down For Low Side Repair To Compressor To service or replace the filter--drier, pump the refrigerant to the condenser and receiver as follows: a.
The presence of moisture in a refrigeration system can d. Under the above conditions, the system is properly have many undesirable effects. The most common are charged when the liquid line sight glase shows full (no copper plating, acid sludge formation, “freezing-up” of bubbles present).
5.10.2 Checking High Or Low Pressure Switches 5.11 FILTER-DRIER WARNING Do not use a nitrogen cylinder without a pres- sure regulator Figure 5- -5 Filter- -Drier Removal Filter-Drier Inlet Liquid Line WARNING Service Valve Solenoid Valve Valve Service Port Filter-Drier Outlet Flare Nut Service Valve Do not use oxygen in or near a refrigeration sys-...
It is not necessary to drain the coolant from the sys- Valve is normally located outside of the tem. AC310/350 rooftop air conditioning system. b. Place main battery disconnect switch in OFF position and lock. There are only three possible valve malfunctions: coil c.
Failure to open may be caused by the following: 1. Coil burned out or an open circuit to coil connections. 2. Improper voltage. 3. Defective plunger or deformed valve body assembly. Failure to close may be caused by the following: 1.
5.15 REPLACING RETURN AIR FILTERS f. Pull filter element approximately 1/4 inch over ends of the diffuser. The return air filters are located behind the return air Diffuser grill, inside the vehicle. The filters should be checked for cleanliness periodically depending on operating conditions. A dirty filter will restrict air flow over the evaporator coil which may cause insufficient cooling or heating and possible frost buildup on the coil.
Figure 5- -14 Thermostatic Expansion Valve Bulb and Thermocouple 1.. Suction Line 4.. Thermocouple Figure 5- -13 Thermostatic Expansion Valve (section view) 5.. TXV Bulb (Shown 1.. Power Head 4.. Gasket 2.. TXV Bulb Clamp in the 4’clock Assembly 5.. Cage Assembly 3..
Page 41
j. The superheat may cycle from a low to high reading. readings taken to determine average superheat. The superheat should be 18 ± 3°F. Monitor the superheat taking readings every 3--5 min- utes for a total of 5--6 readings. Calculate the super- heats, add the readings and divide by the number of k.
Figure 6--7 thru Figure 6--13 shows the CSDD BT324 schematics shown in this section provides information controller used with the AC310 single and dual systems for the AC310 and AC350 model rooftop air conditioning and the AC350 single loop with transit compressors.