Single Chimney Or Flueway; Soot Inspection - Superior MONIA Instructions For Installation, Use And Maintenance Manual

Table of Contents

Advertisement

1.1 SINGLE CHIMNEY OR FLUEWAY

Every appliance must have a vertical fl ue pipe operating by natural draught to
discharge the combustion gases outdoors.
The fl ue must:
- comply with regulations in force in the place of installation of the appliance;
- be tight to the products of combustion, waterproof, suitably insulated, made
with materials resistant to corrosion by the gases and to stress;
- be connected to just one stove, fi replace or extraction hood (Fig. 2);
- be properly sized, with constant free internal section, equal to or greater than
the diameter of the fl ue pipe of the stove and at least 3.5 m in length (Fig. 2);
- be mainly in a vertical position with a defl ection from the axis of no more
than 45° (Fig. 2);
- be at a suitable distance from combustible or fl ammable materials, ensured
by an air gap or suitable insulating material;
- be of uniform internal section, preferably round. Square or rectangular
sections must have rounded corners with a radius of at least 20mm and a
maximum ratio between the sides of 1.5 (Fig. 3-4-5).
- The walls must be smooth if possible and without narrowing. Bends must
be regular and without discontinuity (Fig. 6).
It is forbidden to make fixed or mobile apertures on the flue pipe
to connect appliances other than the one to which it is already
connected.
It is forbidden to pass other air ducts or service pipes inside the
flue pipe, however large it is.
If the flue pipe is an incorrect size or installed other than in
compliance with the above instructions, the factory cannot be
held liable for malfunctioning of the product, damage to property
or injury to persons or animals.

1.2 SOOT INSPECTION

We reccomend that the fl ue must have a chamber for collecting solid matter and any condensate located below the connection and which may be easily
inspected by means of an airtight door. (Fig. 1)
Fig. 2
Fig. 3
Fig. 5
Deposit of creosote
H07023380 / DT2000477-03
Fig. 4
Deposit of creosote
DT2030050-00
Fig. 6
DT2030189-00
DT2010024-02
DT2030049-00
DT2030188-00
DT2030190-00
DT2010031-01
5