General settings

4.1

Time of day and date

4.1.1

Operating principle

The controller has a yearly clock with time of day, weekday and date.
The following time formats are available:
Time format
Date
24 hours
dd.mm.yyyy
(day.month.year)
am/pm
mm / dd / yy
(day/ month/ year)
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Device
Operating line
Time format
Main menu > Time of day / Date
Operating line
Time of day
Date
Year
The change from summertime to wintertime, and vice versa, is made automatically. The
date of the earliest changeover can be adjusted should the relevant regulations change.
The dates set for the change from wintertime to summertime, or from summertime to
wintertime, ensure that on the first Sunday after that date the time of day will change
from 02:00 (wintertime) to 03:00 (summertime), and from 03:00 (summertime) to 02:00
(wintertime).
If both dates are set to coincide, summer-/wintertime changeover will be inactive.
Main menu > Time of day / Date
Operating line
Summertime start
Wintertime start
4.1.2

Communication

For the time of day, there are several sources available, depending on the master
clock. This can be entered on the controller. Time of day and date can be exchanged
via bus.
The following settings for clock time operation are possible:
• Autonomous (does not send and does not receive)
• Time of day via bus: Clock time slave (receives the synchronization signal via bus)
• Time of day on the bus: Clock time master (sends the synchronization signal to the
bus)
Commissioning > Communication > Basic settings >
Boiler Sequence Controller RMK770
4 General settings
Example
Time of day
31.05.2004
hh:mm
(hours: minutes)
05/ 31/ 2 0 04 hh:mm am/pm
(hours : minutes am/pm)
Range
24 hours / 12 hours
(am/pm)
Range
00:00...23:59
01.01...31.12
2000...2100
Range
01.01. ... 31.12
01.01. ... 31.12
Example
15:56
03:56 PM
Factory setting
24 hours
Factory setting
00:00
01.01
2000
Factory setting
25.03
25.10
53/226
CE1P3132en
01.03.2005