4.5

Text entry

4.5.1

Device name and file name

Main menu > Commissioning > Settings > ... or
Main menu > Settings > Texts
Operating line
Device name
The text of the device name appears on the start page in place of "Welcome".
The file name is only of importance in connection with the ACS7... plant operating
software; the text can be edited here.
4.5.2

Aggregate names

Aggregates boiler 1...6, primary controller, heating circuit and time switch can be given
dedicated names. The setting is made on the relevant aggregate.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Boiler 1
Operating line
Boiler 1
Here, text with a maximum of 20 characters can be entered. This designation will then
be used on the info pages and by the menus. Only in the extra configuration and in the
wiring test will the original designation boiler 1 continue to be used.
4.5.3

Text of fault inputs

The texts for the fault inputs are locally displayed as fault texts and are also transmitted
via bus.
In addition to the predefined fault inputs, there are 4 universal fault inputs and 3 digital
aggregate-related fault inputs available. The text for the universal fault inputs can be
edited on Main menu > Settings > Faults, the text for the aggregate-related faults at the
relevant aggregate, e.g. Settings > Boiler 1 > Fault settings.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Faults > Fault input ...
Operating line
Fault text
Fault text
Fault text
Fault text
4.5.4

Electronic business card

The text of the electronic business card is displayed as an Info picture. The electronic
business card must be activated in the extra configuration.
Boiler Sequence Controller RMK770
4 General settings
Range
Free text, max. 20
characters
Range
A...Z
Range
Free text, max. 20
characters
Factory setting
Factory setting
Factory setting
Aux 1
Aux 2
Aux 3
Aux 4
CE1P3132en
01.03.2005