Siemens SIMATIC S5 CP 523 Manual page 201

Serial i/o module
Hide thumbs Also See for SIMATIC S5 CP 523:
Table of Contents

Advertisement

CP 523
FB 200
Segment 1
0000
NAME :SEND
DES
:BADR
I/Q/D/B/T/C: D
DES
:Q-DB
I/Q/D/B/T/C: B
DES
:QANF
I/Q/D/B/T/C: D
DES
:QLAE
I/Q/D/B/T/C: I
DES
:ENDZ
I/Q/D/B/T/C: D
DES
:STAT
I/Q/D/B/T/C: Q
DES
:KBS
I/Q/D/B/T/C: Q
DES
:RKPL
I/Q/D/B/T/C: I
001
:***
STL FB 200
Segment2
001E
001E
:
001F
:
0020
:
0021
:
0022
:
0023
:
0024
:
0025
:=
F 255.0
0026
:
0027
:LW
=BADR
0028
:T
FW 242
0029
:
002A
:
002B
:L
KH 00A0
002D
:DO
FW 242
002E
:T
PY
002F
:L
FW 242
0030
:I
0031
:T
FW 242
0032
:L
KH 0000
0034
:DO
FW 242
0035
:T
PY
0036
:
0037
:DO
FW 242
0038
:L
PY
0039
:T
FY 254
003A
:
003B
:L
KF +0
003D
:T
FY 238
003E
:
EWA 4NEB 811 6044-02a
KM/KH/KY/KC/KF/KT/KZ/KG: KF
KM/KH/KY/KC/KF/KT/KZ/KG: KF
BI/BY/W/D: BY
KM/KH/KY/KC/KF/KT/KZ/KG: KH
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
0
1
0
0
Using the "SEND" and "Receive" Function Blocks
LEN=371
Explanation
-------------------
For CPUs
941
942
943
944
-------------------
Save RLO
Load CP 523 module address
and store
Write KOOR ID
"Read status"
to CP 523 word 0
Fetch acknowledgement
"Read status"
from CP 523 and store
Reset auxiliary flag byte
8-11

Advertisement

Table of Contents
loading

Table of Contents