Serial Interface CP - Peripheral Device
The CP 523 is equipped with an RS-232-C (V.24) interface and a TTY interface. You can set the serial
interface parameters in two ways:
In the user program with job number 90
( 7.3.2).
The CP 523 copies the parameter setting data from the submodule into a RAM area on the CP
during startup. If the CPU transfers new parameter setting data to the CP during operation,
the CP continues with the new data.
In data block 1, parameter block 0, on the user submodule (Print mode
Communications mode 7.3.1).
Data is transferred between the CP and the peripheral device in a 10-bit or 11-bit character frame.
Three data formats are available for each character frame.
10-Bit-character frame
1 start bit, 7 data bits, 2 stop bits
1 start bit, 7 data bits, 1 parity bit, 1 stop bit
1 start bit, 8 data bits, 1 stop bit
11-Bit-character frame
1 start bit, 7 data bits, 1 parity bit, 2 stop bits
1 start bit, 8 data bits, 1 parity bit, 1 stop bit
1 start bit, 8 data bits, 2 stop bits
1st example:
Character frame: 10-bit
Data format: 7 data bits (1 start bit, 7 data bits, 1 parity bit, 1 stop bit)
.:
Bit no
1
0
1 start
bit
Figure 2-3. 10-Bit Character Frame with 7 Data Bits, 1 Parity Bit and 1 Stop Bit
EWA 4NEB 811 6044-02a
2
3
4
5
7 data bits
"Set interface parameters" parameter block
H
(data format 3 in parameter block 0)
(data format 4 in parameter block 0)
(data format 5 in parameter block 0)
(data format 0 in parameter block 0)
(data format 1 in parameter block 0)
(data format 2 in parameter block 0)
6
7
8
9
1
0
1 pari-
ty bit
Technical Description
10
1
1 stop
bit
6.3.1,
2-5