Siemens SIMATIC S5 CP 523 Manual page 127

Serial i/o module
Hide thumbs Also See for SIMATIC S5 CP 523:
Table of Contents

Advertisement

CP 523
Setting Parameters for "3964(R) MODE" via the MEMORY SUBMODULE
When you have decided upon 3964(R) mode, you enter your data in blocks 0 and 7. Enter your
data in the same way as in the other modes. "3964(R)" mode requires additional parameters in
parameter block 7.
Table 7-7. Parameter Block Assignments for 3964(R) Mode
Param-
eter
Block
0
Baud rate
Parity
BUSY signal
Interface
Data format:
11-bit character
frame
10-bit character
frame
HW handshake
EWA 4NEB 811 6044-02a
Description
110 Bd
200 Bd
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
even
odd
"mark"
"space"
no parity check
TTY
V.24 (RS 232 C)
Parity:
7 data bits
(yes)
8 data bits
(yes)
8 data bits
(no)
7 data bits
(no)
7 data bits
(yes)
8 data bits
(no)
OFF
Value Range
1
2
3
4
5
6
7
8
0
1
2
3
4
No
0
0
1
0
1
2
3
4
5
0
ON
1
Communications Mode
Default Values
on the CP 523
4
0
0
0
0
0
7-21

Advertisement

Table of Contents
loading

Table of Contents