Commissioning
3

Basic commissioning with the wizard

3.4
24
Siemens AG
Basic commissioning with the wizard
There are essentially four steps to commissioning with the wizard:
1. Reset to factory settings
Restore the drive to the factory settings. This ensures that the drive is in a
defined basic setting.
2. Execute basic commissioning with the wizard
Basic commissioning includes all the important settings. You can check the
data before saving the settings using the wizard.
3. Change the most important settings manually (optional)
You can then change the settings of your drive once again.
4. Create a backup copy of the data on a memory card (MMC or SD).
NOTICE
The drives are preset in the factory for applications using 4-pole three-phase
induction motors that correspond to the performance data of the drive.
If you are using the STARTER commissioning tool and a Siemens motor,
enter the order number for the motor. The data is applied automatically.
If you are not using a Siemens motor, read the data from the motor's rating
plate and enter the appropriate parameters manually.
Example: Rating plate details and their assignment to the drive parameters:
NOTICE
The entry of the rating plate data must match the interconnection of the motor
(star (wye) circuit [Y] / delta circuit [Δ]).
Enter the delta rating plate data in the case of a motor delta circuit.