Control Drawing Sc202S Ma Hart ® Specification (Iecex) - YOKOGAWA SC202G User Manual

2-wire conductivity or resistivity transmitter
Hide thumbs Also See for SC202G:
Table of Contents

Advertisement

2-6 Specifications
2-4. Control Drawing SC202S mA HART ® Specification (IECEx)
Intrinsically safe design
IEC Ex standard Ex ia IIC : T4 for ambient temp. < 55°C
C ertificate nr. IEC Ex KEM 06.0053X
SC 202S
(C onductivity/R esistivity-transmitter)
+
_
G
SENSO R (S)
term inals 11-16
Hazardous area
Zo ne 0 o r 1
Intrinsically safe design
IEC Ex standard Ex ia IIC : T4 for ambient temp. < 55°C
C ertificate nr. IEC Ex KEM 06.0053X
SC 202S (C onductivity/R esistivity-transmitter)
+
_
G
SEN SO R(S)
term inals 11-16
Hazardous area
Zone 0 or 1
・ Sensor(s) are of a passive type to be regarded as 'simple apparatus'.
・ Electrical data of the SC202S.
- Supply and output circuit (terminals + and -):
Maximum input voltage U
Maximum input power P
Effective internal capacitance
Effective internal inductance
- Sensor input circuit (terminals 11 through 16):
Maximum output voltage U
Maximum allowed external capacitance
Maximum allowed external inductance
・ Barriers and power supply specification must not exceed the maximum values
as shown in the diagram above. These safety descriptions cover most of
the commonly used industry standard barriers, isolators and power supplies.
・ The Hand Held Communicator must be of a IECEx certified intrinsically safe type
in case it is used on the intrinsically safe circuit in the hazardous area or of a
IECEx certified non-incendive type in case it is used in the non-incendive circuit
in the hazardous area.
IM 12D08B02-01E
T6 for ambient temp. < 40°C
Functional
Functional
earth
earth
Safe area
T6 for ambient temp.< 40°C
Functional
earth
= 31.5 V.
i
= 1.2 W.
i
= 14.4 V.
o
Ex ia or ib
C ertified safety barrier or pow er
w ith R int=300
(HAR T compatible)
U o = 31.5 V olt D C
Io = 100 mA
Load
R esistance
Ex ia or ib C ertified R epeater
Pow er Supply
(HAR T C ompatible)
+
_
U o = 31.5 V olt D C
Io = 100 mA
Po = 1.2 W att
Safe area
Maximum input current I
C
= 22 nF.
i
L
= 35 H.
i
Maximum output current I
Co = 59 nF (for SC202S-A),
Co = 2.9 F (for SC202S-N).
Lo = 200 mH (for SC202S-A),
Lo = 450 mH (for SC202S-N).
24 volts D C N ominal
Supply V oltage.
+
_
O utput
Supply
= 100 mA.
i
= 13 mA.
o

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents