System Settings - Mitsubishi Electric AE-200A Instruction Book

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

5-3-2. System Settings

To use Integrated Centralized Control Web, you need to configure the settings using Initial Setting Tool.
Refer to the AE-200/AE-50/EW-50 Instruction Book (Initial Settings) for details.
Important
● When using Initial Setting Tool, be sure to configure the settings as described in the procedures of Instruction Book (Initial
Settings).
[1] Settings of the centralized controllers to be managed with Integrated Centralized Control Web
Use Initial Setting Tool to configure the settings of the centralized controllers to be managed with Integrated
Centralized Control Web.
(1) In [Basic Settings] > [System Configuration] of Initial Setting Tool, specify the IP address of each centralized
controller to be managed with Integrated Centralized Control Web.
(2) In [Floor Settings] > [Floor for Integrated Centralized Control Web], set the login destination centralized
controller (target centralized controller) of Integrated Centralized Control Web and the management target
centralized controllers (managed centralized controllers).
Note: When connecting an AE-200/AE-50/EW-50 to an existing LAN, consult the system administrator to decide the IP addresses.
Note: When using an AE-200/AE-50/EW-50-dedicated LAN, it is recommended that the AE-200 unit be assigned an IP address
between the range [192.168.1.1] and [192.168.1.40], and the AE-50/EW-50 unit be assigned an IP address between the range
[192.168.1.211] and [192.168.1.249].
[2] Floor settings
Configure the floor layout settings, referring to 5-2-11 "Floor Layout settings on the Integrated Centralized Control
Web" or the Instruction Book (Initial Settings).