Software Update; Preparation - Mitsubishi Electric AE-200A Instruction Book

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

6-3. Software Update

The AE-200/AE-50/EW-50 software can be updated by either directly reading the update file in a USB memory
device or by using a Web browser.
① Directly reading the update file in a USB
memory device
USB
This manual explains how to update the software by directly reading the update file in a USB memory device ( ① ).
For how to update the software using a Web browser ( ② ), refer to the Instruction Book (Initial Settings).

6-3-1. Preparation

Store the update file (AExx_FW####_****.dat)
*1 "xx": "200" (AE-200) or "50" (AE-50); "####_****": software version
Caution:
Obtain an approval from the client for the following precautions as necessary.
1. The communication between AE-200/AE-50/EW-50 and the air conditioning units will stop while
the software is being updated. Although the unit in operation may detect a communication error
and an error sign may appear on the local remote controllers, the unit will continue its operation
and be operable from the local remote controllers.
* Note that Mr. Slim indoor units or systems with no local remote controllers may detect a communication error and come
to an abnormal stop.
2. Record the operation status of the air conditioning units immediately before updating the
software. After the software update completes, check the operation status of the units, and
manually operate the units as necessary.
3. Some operations and functions, such as scheduled operations, billing function, Peak Cut control,
energy management function, will be disabled while the software is being updated. Check the
setting details of these functions beforehand, and update the software when it does not affect
these functions.
4. If the functions in the table below are used on the TG-2000A, avoid updating the software during
the time period indicated in the right column.
TG-2000A function in use
Electricity charge apportioning function
Malfunction log backup
Peak Cut data backup
Measurement trend data backup
5. CSV output data (e.g., energy management data) will lose up to 60-minute worth of data.
6. When a built-in PI controller is used, pulse signals cannot be input while the software is being
updated.
WT07982X03
② Using a Web browser
PC for update
USB
CD
*1
in the root folder of a USB memory device.
Time period in which the update is prohibited
AM 4:05 – 4:35
AM 0:05 – 0:15
AM 2:00 – 2:10
AM 1:05 – 1:15
86
LAN
HUB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae-50aAe-200eAe-50e

Table of Contents