Toshiba RAS-3M18S3AV-E Service Manual page 94

Split type
Hide thumbs Also See for RAS-3M18S3AV-E:
Table of Contents

Advertisement

11-8. Inspection of the Main Parts
[1] Sensor characteristic table
100
90
80
70
60
50
40
30
20
10
0
0
10
Outdoor Unit
No.
Part name
1
Compressor
(Model : DA136A1T-40N)
2
Outdoor fan motor
(Model : ICF-140-43-4R)
Compressor thermo. Bimetal type
3
(Model : CS-12AL)
4
High pressure switch
(Model : ACB-4UB83W)
5
Outdoor temperature sensor (TO),
pipe temperature sensor
(TGa, TGb, TGc), discharge
temperature sensor (TD), suction
temperature sensor (TS),
evaporator temperature sensor
(TE),
TD
TO, TE, TS, TGa to TGc
20
30
40
50
Temperature (˚C)
Measure the resistance value of each winding by using the tester.
White
Measure the resistance value of winding by using the tester.
White
Check conduction by using the tester.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)
Sensor
TO, TE, TS (kΩ)
TGa to TGc (kΩ)
TD
: Discharge temp. sensor
TO
: Outdoor temp. sensor
TE
: Outdoor heat exchanger temp. sensor
: Suction temp. sensor
TS
TGa to TGc : Gas side temp. sensor
Checking procedure
Red
Position
Red - White
White - Black
Black - Red
Black
Red
Position
Red - White
White - Black
Black - Red
Black
Temperature
10°C
TD (kΩ)
105
20.6
20.0
- 94 -
FILE NO. SVM-15102
Resistance value
0.68 ± 0.03Ω
Under 20°C
Resistance value
21 ± 1.05Ω
For details, refer to Section 11-10.
20°C
25°C
40°C
64
51
27
12.6
10.0
5.1
12.5
10.0
5.3
50°C
18
3.4
3.6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents