Toshiba RAS-3M18S3AV-E Service Manual page 85

Split type
Hide thumbs Also See for RAS-3M18S3AV-E:
Table of Contents

Advertisement

Check
Outdoor
code
LED display
*
[1C]
*
*
[14]
** *
[16]
* 
[17]
:ON ( *:3 sec ON / 0.5 sec OFF) :OFF
(Item without special mention indicates part of outdoor unit.)
[Case thermo operation, Power supply error ]
Is AC mains voltage correct?
(198 to 264V)
YES
Are CN609 of P.C. board MCC-1645
connection and case thermostat correct?
YES
Short each pins of CN500.
Can compressor operate?
YES
Is there gas leak?
Is there refrigerant shortage?
NO
Is service valve fully opened?
YES
Is PMV under correct conditions?
YES
[Short-circuit of compressor drive element]
Are connections of
compressor lead and reactor correct?
(Check referring to the Wiring diagram.)
YES
Does the same error occur in operation
without compressor lead?
NO
[Position detection circuit error]
Check outdoor P.C.B MCC-1645.
Defect → Replace.
[Current detection circuit error]
Check outdoor P.C.B MCC-1645.
Defect → Replace.
- 85 -
Check and troubleshooting
NO
NO
Case thermostat error → Replace.
NO
Check ourdoor P.C.B MCC-1645.
YES
NO
NO
Defect → Correct and Replace.
NO
YES
Replace outdoor P.C.B MCC-1645.
Check compressor. (Rare short, etc.)
FILE NO. SVM-15102
Confirm power supply
construction. etc.
Correct connector.
Defect → Replace.
Repair defective position.
Recharge refrigerant.
Open service valve fully.
Correct defective position.
Replace defective part.
Check crushed or broken pipe.
Correct wiring.
Defect → Replace.