Toshiba RAS-3M18S3AV-E Service Manual page 108

Split type
Hide thumbs Also See for RAS-3M18S3AV-E:
Table of Contents

Advertisement

No. Part name
High pressure 1.Detachment
switch
1) Perform work of ①.
2) Recover the refrigerant gas form the outdoor unit.
3) Perform work of ②, ③, ④ and ⑤.
4) Remove the sound-insulation material and partition.
5) Remove the high pressure switch by the burner.
Take care that the electric parts, 4 way valve,
butyle, compressor, accum tank, heat exchanger,
and etc. are not caught by flame.
(Otherwise pperation trouble may occur.)
1.Attachment
・Be sure not to burn lead wire of the high pressure
switch.
Adjust the temperature of the hight pressure
switch to below 100
the wet towel for cooling.
Use the protective plate for the brazing.
Procedure
C during the brazing. Use
º
High pressure switch
Wet towel
- 108 -
FILE NO. SVM-15102
Remarks
Protective plate

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents