Toshiba RAS-3M18S3AV-E Service Manual page 65

Split type
Hide thumbs Also See for RAS-3M18S3AV-E:
Table of Contents

Advertisement

10-2. Outdoor Unit
10-2-1. Accessory and Installation Parts
Installation manual
F-GAS label
∗1
∗1 Part that do not exist in RAS-2M18S3AV-A,-TR, RAS-2M14S3AV-TR
10-2-2. Refrigerant Piping
• Piping kit used for the conventional refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more thickness.
• Flare nut and flare works are also different from those of the conventional refrigerant.
Take out the flare nut attached to the main unit of the air conditioner, and use it.
10-2-3. Installation Place
• A place which provides the spaces around the outdoor unit.
• A place where the operation noise and discharged air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place which does not block a passageway.
• When the outdoor unit is to be installed in an elevated position, be sure to secure its feet.
• There must be sufficient spaces for carrying the unit into and out of the site.
• A place where the drain water does not raise any problem.
• A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration.
10-2-4. Installation Parts (Local Supply)
Parts name
Refrigerant piping ∗1
Putty, PVC tapes
∗1 Refrigerant piping covered with insulating material (Polyetylene form, 6 mm thick).
When duct-type or cassette-type unit is to be installed, it shall be covered with thicker insulating material
(Polyetylene form, 10 mm thick).
* Example of indoor unit class: RAS-B10UFV-E1 is abbreviated as "10".
Indoor unit class
Unit C
07 or 10 or 13
Unit B
07 or 10 or 13 or 16
Unit A
07 or 10 or 13 or 16
36 (3M18)
Total
32 (2M18)
26 (2M14)
Rubber cap
1
(Water-proof)
1
Drain nipple
Indoor unit (abbreviation)
07, 10, 13
16
Standard connecting pipe diameter
3M18
2M18
6.35, 9.52 mm
6.35, 9.52 mm
6.35, 9.52 mm
*3
6.35, 12.7 mm
6.35, 9.52 mm
*2
2
1
Parts name
Liquid side (O.D.)
6.35 mm
6.35 mm
2M14
*3
6.35, 9.52 mm
6.35, 9.52 mm
*3
- 65 -
FILE NO. SVM-15102
CD-ROM
(Installation manual)
∗1
Gas side (O.D.)
9.52 mm
12.7 mm
All combinations that do not exceed the "Total" number
can be installed.
2 or more indoor units must be connected to an outdoor
unit.
When 2 indoor units are connected to an outdoor unit,
note that some combinations of indoor units are not
compatible.
For the further details, refer to the catalogue.
*2 Need the reducer (07, 10, 13 class 12.7 to 9.52 mm).
*3 Need the expander (16 class 9.52 to 12.7 mm).
• Locally procured.
1