Motor data identification
Before the inverter can be operated, you must start the motor from the PC. Performing
this action will activate the parameters. The first step is to assume control priority.
1
Open the "Commissioning" entry in the project tree.
2
Double-click "Control panel" to open the control panel in the workbench area.
3
In the workbench area, click on "Assume control priority."
1
STARTER software and PC:
56
2
3
Parameterization
The pending motor data
identification is indicated
by the message "warning
541" in the workbench. You
can find the message in the
alarm tab. It tells you that
motor data identification
will be performed after
switching the motor on.
Note