Step 1521-8
Is the error code that sent you to this MAP still reported?
The problem has been corrected. Go to "MAP 0410: Repair Checkout" in the RS/6000 and
NO
Eserver pSeries Diagnostic Information for Multiple Bus Systems.
YES
Call for support. This ends the procedure.
Step 1521-9
Note: Read the Danger and Caution notices under "Safety Notices" on page vii before continuing with this
procedure.
1.
Prepare a multimeter to measure up to 600 V ac.
2. Use the multimeter to measure the ac voltage at the test points on the frame labeled Phase A and
Phase B.
Is the ac voltage greater than 180 V ac?
NO
Inform the customer that the line voltage into the BPA is missing or too low. This ends the
procedure.
YES
Independent faults are indicated on both sides of the BPA. Each side must be isolated separately.
Call for support. This ends the procedure.