Maintenance, And Overhaul Generator Set - Hobart TM416 Operation And Maintenance Instruction Manual

Table of Contents

Advertisement

OPERATION,
MAINTENANCE,
AND
OVERHAUL
MANUAL
TM-41
I,
MOTOR-DRIVEN
GENERATOR
SET,
SEi; IES Z5C;1A Ah D sso;lA
(4)
Vibration
trouble
shooting
Because
of the complex
nature
of vibratim
and
rescnance,
it may be necessary
to change
'the typeand
locatim
of mounts to achieve
the best results
m a
particular
machine.
C,
Wiring
the Generator
Set
(1)
Power input wiring
WARNING:
ALWAYS
BE SURE THE POWER SOURCE
IS TURNED
OFF WHEN
WCRKING
ON
INPUT
LEADS OR CONNECTIONS.
Connect
a source
of power at input terminal
panel
(Ref.
Fig.
1).
Connect
460-V,
3-phase,
60-Hz
to Series 5503A,
except
S-5503A-5
Connect
575-V,
3-phase,
60-Hz
to S-5503A-5
Connect
380-V,
3-phase,
50-Hz
to Series 5507A
See
1-1,
Fig.
2 for cablesize.
A disconnect
switch
and fuses must be installed
in the input circuit
between
the power source and the generator
set.
Route the input
leads (cable or cm-
duit)
carefully
so they
will
not be a hazard
to personnel,
and not be subject
to wear and damage by wheeled
vehicles
and equipment.
See l-l,
Fig.
2
for recommended
cable
and fuse sizes;
however,
minimum
cablesize
must
cmform
to local
electrical
code.
Proper rotation
of the motor is C LOC KWISE
when viewed
from the front,
motor end (see arrow
m pushbutton
switch
panel).
If leads are not identified,
connect
at random and use a phase rotatim
meter
to determine
proper phase sequence.
If out of phase,
change
any two input
leads to correct,
If a phase rotation
meter
is not available,
check
for correct
rotation
as follows:
(a)
Remove
cne of the canopy
sides at the motor end so that the direction
of motor rotation
may be observed.
Feb 27/76
l-2
Page 3