Electrical Trouble Shooting Chart - Hobart TM416 Operation And Maintenance Instruction Manual

Table of Contents

Advertisement

OPERATIOti;
MdlNTENANCE,
AtiD
OVERHAUL
MANUAL
TM-416
MOTOR-DRIVEN
GENERATOR
SET,
SEZIES 5503A
AND
5507A
:
TROUBLE,
SYMFTGM
v
TEST,
CHECK,
AND
AND
COND
IT IGN
PROBABLE
CAUSE
REMEDY
MOTOR
CbNTROLS
t
1. Motor
will
not start whe
START button
is pushed.
Indicating
light
(1 A)
does
NCT
glow.
A. No input
power
to
term inal panel
(1) Remotely
locatec
1
disconnect
switcl
OFF.
(2) Input
line
fuse
"blown"
or input
circuit
breaker
(if useb) 'tripped.
B. Overload
relay
(1 OL)
tripped.
C. Overload
relay
(1GL)
contacts
or
operating
mechanisn
defective.
D. Control
transformer
overload
relay
(20L)
defective.
E. Control
transformer
(1T) defective.
A.
B.
s
- . .
1.
.
Restore power,
(1)
Turn switch
ON.
(2)
Replace
fuse or reset cir-
cuit
breaker.
Check
input
circuit
for loose connecfioi
or short circuit.
Repair
before
operating
unit.
Check
voltage
between
TP
(test point)
107 and TP 108.
If
indicated
input voltage
is near
normal
(see l-l;
Fig.
2) for the
machine,
overload
relay
('IOL)
has tripped
and has not reset.
See
"C " be low.
Check
voltage
between
TP 107
and TP 108.
If a voitaae
is
indicated,
contacts
are de-
fective.
Replace
overload
relay
(1 OL).
Check
voltage
between
TP 111
and TP 112.
A voltqe
oi 115
V AC indicates
relay
(2CL?
is defective.
Replace
relay.
Check
for correct
connecticn
to transformer
taps.
See motor
schematic
diagram,
Fig.
1.
Check
for normal,
115 V AC
between
TP 110 and TP ! 11.
If voltage
is abnormal,
+rans-
for&r
is defective.
Replace,
Feb 27/26
Electrical
Trouble
Shooting
Chart
Figure
5 (Sheet
1 of 17)
3-1
Page 7