Parameter list
7.2 Parameter list
Parameter
Function
Dependency:
P2802[0] assigns the timer to the processing sequence.
P2850
Delay time of timer 1 [s]
Defines delay time of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
Dependency:
See P2849
P2851
Mode timer 1
Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
0
1
2
3
10
11
12
13
Dependency:
See P2849
r2852.0
BO: Timer 1
Displays output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853. See
r2811 for the bit field description.
Dependency:
See P2849
r2853.0
BO: Nout timer 1
Displays Not-output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are r2852, r2853.
See r2811 for the bit field description.
Dependency:
See P2849
P2854
BI: Timer 2
Define input signal of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
Dependency:
P2802[1] assigns the timer to the processing sequence.
P2855
Delay time of timer 2 [s]
Defines delay time of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
Dependency:
See P2854
P2856
Mode timer 2
Selects mode of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See P2851 for value description.
Dependency:
See P2854
r2857.0
BO: Timer 2
Displays output of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858. See
r2811 for the bit field description.
Dependency:
See P2854
r2858.0
BO: Nout timer 2
Displays Not-output of timer 2 P2854, P2855, P2856 are the inputs of the timer, outputs are r2857, r2858.
See r2811 for the bit field description.
Dependency:
See P2854
266
Range
Factory
Can be
default
changed
0.0 - 9999.9 0.0
U, T
0 - 13
0
U, T
ON delay (seconds)
OFF delay (seconds)
ON / OFF delay (seconds)
Pulse generator (seconds)
ON delay (minutes)
OFF delay (minutes)
ON / OFF delay (minutes)
Pulse generator (minutes)
-
-
-
-
-
-
0 -
0
U, T
429496729
5
0.0 - 9999.9 0.0
U, T
0 - 13
0
U, T
-
-
-
-
-
-
Scaling
Data
Data
set
type
-
-
Float
-
-
U16
-
-
U16
-
-
U16
-
-
U32
-
-
Float
-
-
U16
-
-
U16
-
-
U16
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Acc.
Level
3
3
3
3
3
3
3
3
3