Siemens SINAMICS V20 Operating Instructions Manual page 217

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
Note:
P1300 = 1: V/f with FCC (flux current control)
Maintains motor flux current for improved efficiency
If FCC is chosen, linear V/f is active at low frequencies
P1300 = 2: V/f with a quadratic characteristic
Suitable for centrifugal fans / pumps
P1300 = 3: V/f with a programmable characteristic
User defined characteristic (see P1320)
P1300 = 4: V/f with linear characteristic and Economy Mode
Linear characteristic with Economy Mode
Modifies the output voltage to reduce power consumption
P1300 = 5,6: V/f for textile applications
Slip compensation disabled.
Imax controller modifies the output voltage only.
Imax controller does not influence the output frequency.
P1300 = 7: V/f with quadratic characteristic and Economy Mode
Quadratic characteristic with Economy Mode
Modifies the output voltage to reduce power consumption
P1300 = 19: V/f control with independent voltage setpoint
The following table presents an overview of control parameters (V/f) that can be modified in relationship to
P1300 dependencies:
P1310[0...2]
Continuous boost [%]
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
Can be
default
changed
0.0 - 250.0
50.0
U, T
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
PERCEN
DDS
Float
T
Acc.
Level
2
217

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents