Power On/Off Procedures; Safety And Environmental Information; Standby Mode; Power On Procedures - HP HPE XP P9500 Manual

Hide thumbs Also See for HPE XP P9500:
Table of Contents

Advertisement

4 Power On/Off procedures

Safety and environmental information

CAUTION:
theP9500 site preparation guide and the environmental information in ???.

Standby mode

When the disk array power cables are plugged into the PDUs and the PDU breakers are ON,
the disk array is in standby mode. When the disk array is in standby mode:
The Basic Supply (BS) LED on the control panel is ON. This indicates that power is applied
to the power supplies.
The READY LED is OFF. This indicates that the controller and drive chassis are not
operational.
The fans in both the controller and drive chassis are running.
The cache destage batteries are being charged.
The disk array consumes significantly less power than it does in operating mode. For example,
a disk array that draws 100 amps while operating draws only about 70 amps in standby
mode (see
To put the disk array into standby mode from the OFF condition:
1.
Ensure that power is available to the AC input boxes and PDUs in all racks in which the
P9500 disk array is installed.
2.
Turn all PDU power switches/breakers ON.
To put the disk array into standby mode from a power on condition, complete the power off
procedures in this chapter. See
To completely power down the disk array, complete the power off procedures in this chapter,
then turn off all PDU circuit breakers.
CAUTION:
before turning off the PDU circuit breakers. Otherwise, turning off the PDU circuit breakers can
leave the disk array in an abnormal condition.
Power On/Off procedures
This section provides general information about power on/off procedures for the P9500 disk
array. If needed, consult Hewlett Packard Enterprise Technical Support for assistance.

Power On procedures

CAUTION:
power to the disk array.
Prerequisites
Ensure that the disk array is in standby mode. See
NOTE:
The control panel includes a safety feature to prevent the storage system power from
accidentally being turned on or off. The PS power ON/OFF switch does not work unless the
ENABLE switch is moved to and held in the ENABLE position while the power switch is moved
to the ON or OFF positions.
46
Power On/Off procedures
Before operating or working on the P9500 disk array, read the safety section in
"Electrical specifications" (page
"Power Off procedures" (page
Make certain that the disk array is powered off normally and in standby mode
Only a trained Hewlett Packard Enterprise support representative can restore
55)) for power consumption specifications.
47).
"Standby mode" (page
46).