Figure 5 Example P9500 disk array configurations

Electrical specifications

"System heat and power specifications" (page 22)
specifications " (page 22)
components.
Table 10 System heat and power specifications
Heat Dissipation
and Power
Consumption
Specifications
(Maximum
configuration)
1
Heat (KW, BTU, Kcal) and Power (kVA) values are for determining load for site planning. Actual heat generation
and power demand may be less.
2
Calculated values with drives at a typical I/O condition. (Random Read and Write, 50 IOPSs for HDD, 2500 IOPSs
for SSD, Data Length: 8Kbytes). These values may increase for future compatible drives.
Table 11 System components heat and power specifications
Component Product
Number
AV375A
AV392A, AV393A
AV400A
AV401A, AV401B
AV402A,AV402B
AV411B
22
Installation requirements
list the heat and power specifications for the P9500 disk array and
1, 2
Parameter
DKC Module-0
Max Power
5.87
consumption
(kVA)
Max Heat
5.57
dissipation (kW)
Max BTUs per
19012
hour
Max Kcal per hour
4791
P9500 Disk Array Component
Flash Module Chassis
Flash Module
Disk Array DKC Module-0 Rack
DKC Module-1 Rack
DKU Disk Unit Rack
Base 2.5in Drive Chassis
and
"System components heat and power
DKC Module-1
DKU Rack
5.42
5.45
5.15
5.17
17571
17643
4428
4446
Heat Output
1
(kW)
4
0.600
3
0.017
1.88
1.83
1.47
see note 5
Full Array
(DKC-0 plus
DKC-1 plus DKU
x4)
33.1
31.4
107155
27002
Power
Consumption
1
(kVA)
4
0.640
3
0.018
1.97
1.93
1.54
see note 5