The RUGGEDCOM RS900GP has passed the following EMI and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEC 60255-5
IEEE 1613 Type Tests
NOTE
The RUGGEDCOM RS900GP meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
34
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
Enclosure
Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power Ports
Earth
Ground Ports
Signal ports
± 2 kV line-to-earth,
± 1.5 kV line-to-line
DC Power Ports
± 2 kV line-to-earth, ± 1 kV line-to-line
Signal ports
DC Power Ports
Earth
Ground Ports
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
DC Power Ports
30% for 0.1 s, 100% for
0.02 s, 100% for 0.05 s
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
DC Power Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal ports
30 V Continuous, 300 V for 1s
DC Power Ports
30 V Continuous, 300 V for 1s
DC Power Ports
Signal ports
1.5 kV (Fail-Safe Relay output)
DC Power Ports
Signal ports
5 kV (Fail-Safe Relay output)
DC Power Ports
RUGGEDCOM RS900GP
Installation Guide
Test Levels
Severity Levels
± 8 kV
± 15 kV
20 V/m
± 2 kV
± 1.5 kV
± 2 kV
10 V
10 V
10 V
15%
2 kV
5 kV
EMI and Environmental Type Tests
4
4
x
4
x
3
4
3
3
3
3
3
3
4
4
4