Room Temperature Setpoint; Flow Temperature Setpoint - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Important
Benefit
Description
Setting
Note
Benefit
Description
Setting
Note
Siemens Building Technologies
HVAC Products
1)
Setpoints and readjustments made on room units are considered only in automatic
mode
.
4.17

Room temperature setpoint

Information about the room temperature setpoint in the various operating modes
Displays the current room temperature setpoint during the respective heating period
(normal operation / reduced operation).
1.
Press the operating line selection buttons to select line 71.
2.
No setting can be made with the + / - buttons.
Display
0...35
When selecting the operating line, the current room temperature setpoint is displayed,
depending on the operating mode and the time switch program, that is, a selection /
combination of the following parameters:
Room temperature setpoint knob
Reduced setpoint of room temperature (operating line 13)
Frost protection setpoint of room temperature (operating line 15)
Readjustments made on the room unit (QAA50 / QAA70)
If there is no heating circuit, the display shows "---".
4.18

Flow temperature setpoint

Displays the current flow temperature setpoint of the pump heating circuit
When selecting this operating line, the current flow temperature setpoint of the
controller's internal pump heating circuit is displayed.
1.
Press the operating line selection buttons to select line 72.
2.
No setting can be made with the + / - buttons.
Display
0...140
The value displayed corresponds to the flow temperature of the pump heating circuit
which is required for reducing the demand for heat.
The display shows "---" in the following situations:
No heating circuit available
ECO function active (summer / winter changeover, automatic 24-hour heating limit)
Quick setback active
Room temperature limitation active
Basic Documentation RVA47.320
Description of the heating engineer settings
Unit
°C
Unit
°C
69/166
CE1P2379E
15.07.2002