Actual Value Of The Cascade Return Temperature - Siemens RVA47.320 User Manual

Cascade controller for modulating gas-fired boilers
Table of Contents

Advertisement

Special displays
Description
Setting
Effect
Cascade return
temperature sensor
Siemens Building Technologies
HVAC Products
1
B10
Cascade flow temperature sensor
– – –
Sensor with open-circuit, no sensor connected, or sensor incorrectly
defined
0 0 0
Sensor with short-circuit
4.7
Actual value of the cascade return
temperature
When using several cascaded heat sources, we recommend to use a cascade return
temperature sensor (B70).
It is also termed "Common return temperature sensor".
1. Press the operating line selection buttons to select operating line 57.
2. No setting can be made with the + / - buttons.
Display
0...140
The temperature measured with the cascade return temperature sensor (B70) will
automatically be displayed on this line.
In a cascaded system, a common cascade return temperature sensor (B70) should be
used for all heat sources. The value of this sensor is used for optimizing the controller's
functionality. In particular, it permits the detection of wrong mass flows (primary /
secondary mass flow).
The cascade return temperature sensor is connected directly to the RVA47.320.
Basic Documentation RVA47.320
Description of the heating engineer settings
2
3
Unit
°C
B10
4
B70
61/166
CE1P2379E