2.4

Parameter settings for the enduser

The following settings can be made to meet the individual needs of the enduser.
Buttons
Explanation
1
Press one of the line selection buttons.
This will take you directly to the programming level
"Enduser".
2
Press the line selection buttons to select the required
line.
The parameter list on the next pages contains all
available lines.
3
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.
4
By pressing any of the operating mode buttons, you
leave the programming level "Enduser".
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
Basic Documentation RVA47.320
Handling
Note:
Line
• • •
Contin.
display
CE1P2379E
15.07.2002