Heating circuit values

3.12

Reduced room temperature setpoint

Lower room temperatures during non-occupancy times, e.g. during the night
Energy savings
The heating system has 3 different setpoints that can be adjusted:
The reduced room temperature setpoint described here.
The nominal room temperature setpoint (to be adjusted with the setpoint knob).
The frost protection setpoint of the room temperature (setting on operating line 15)
1. Press the operating line selection buttons to select line 14.
2. Press the + / – buttons to adjust the reduced room temperature setpoint.
Setting range
TRF...TRN
TRF
Frost protection setpoint of the room temperature (setting on line 15)
TRN Nominal room temperature setpoint (to be adjusted with the setpoint knob)
If the required temperature level cannot be set, the adjustment made with the setpoint
knob may be too low. It is not possible to set a value above the adjustment made with
the setpoint knob.
0
2
4
6
Room temperature setpoint setting ranges
14
Setting "Reduced room temperature setpoint "
15
Setting "Frost protection setpoint of the room temperature"
With this setting, the reduced room temperature setpoint will change to the level called
for by reduced operation
Mo
...
So
0
2
4
The heating periods are in accordance with the settings made on lines 6 to 11.
Basic Documentation RVA47.320
Description of the enduser settings
Unit
°C
8
10
12
14
16
in the living rooms.
6
8
10
12
Factory setting
16
18
20
22
24
14
16
18
20
22
2379Z17
26
°C
2373Z11
24 h
43/166
CE1P2379E
15.07.2002