Device address
Note
Siemens Building Technologies
HVAC Products
LPB / system
•
Creation of systems
•
Wide field of use with a smaller number of unit versions
•
Plants can be extended in a straightforward manner
The LPB is used as a communication basis for generating a system with additional
ALBATROS™ controllers or controllers of other manufacture.
4.50
LPB device address
The device address and the segment address are used as destinations in the bus
system (similar to a postal address). To ensure communication, each device must be
correctly addressed.
1.
Press the operating line selection buttons to select operating line 140.
2.
Press the + / - buttons to enter the device number.
Setting range
0...16
Entry of the device address is especially important when using combinations of units, or
in a system. The addresses classify the controllers within a segment.
Entry:
Address
Effect
0
Standalone
1
Master (LPB)
2...16
Slave (LPB)
The device addresses should be assigned in consecutive order in accordance with the
controllers connected. It is not permitted to assign an address several times within a
bus segment, since this would lead to communication errors. Each segment must have
a device as a master (address 1).
For more detailed information about the addressing of devices in a system, refer to
"Local Process Bus (LPB), Basic Documentation, System Engineering" (document no.
CE1P2370E).
Basic Documentation RVA47.320
Description of the heating engineer settings
Unit
Increment
Example
Single controllers
−
Controllers with master function
−
Cascade master
−
Heat generation master
−
Consumer master in the respective segment
−
Controllers with slave function
−
Other heat generation controller
−
Heating circuit controller
−
D.h.w. controller
Factory setting
1
99/166
CE1P2379E
15.07.2002