3. Project guidance

3.1
Sizing table
(DN 6 to DN 2000)
3. Project guidance
The table shows the relationship between flow velocity V, flow quantity Q and sensor dimension
DN.
Guidelines for selection of sensor
Min. measuring range: 0-0.25 m/s
Max. measuring range: 0-10 m/s
Normally the sensor is selected so that V lies within the measuring range 1-2 m/s.
Flow velocity calculation formula:
1273.24 x Q [l/s]
V =
[m/s]
2
DN
[mm]
DKFD.PS.027.W3.02
3
353.68 x Q [m
/h]
or V =
2
DN
[mm]
[m/s]