Modbus Slave (RTU Mode)

11-1-1 Basic Formats

Commands
PT slave address
Function code
Responses
PT slave address
Function code
The formats for sending commands from the Modbus-RTU master to the PT
and for returning responses from the PT are given below. The maximum
length of commands or responses supported by the NV-series PTs is 512
bytes.
Data
Data
PT Slave Address
Specify the slave address set in the PT (1 to 247). However, a maximum of 31
PTs can be connected. The Modbus-RTU master can communicate with only
one PT at a time. The slave address can be set to 0 for some function codes
to specify broadcast mode. If 0 is specified, the command will be received by
all slaves regardless of their specified slave numbers. Responses are not
returned for broadcast commands.
Function Code
The function to be executed by the Modbus-RTU master is specified with the
function code. The NV-series PTs support the following function codes.
Function
code (hex)
01
Read internal bit status
03
Read holding register con-
tents
04
Read input register contents
05
Write single internal bit
06
Write data register, one word
0F
Write multiple internal bits
10
Write multiple data registers
Data
The data required for the command is sent. The data that is required depends
on the function code.
Error Check
CRC-16 (cyclic redundancy check) error checking is performed.
Error check
Error check
Function
Broadcast
mode
Supported. GR/WGR
Supported. GDT
Supported. GR
Supported. GDT
Section 11-1
Applicable internal
memory specifications
GR/WGR
GDT
GDT
99