Installing The Boiler - Ariston GENUS HE SYSTEM 24 Installation And Servicing Instrucnions

Gas fired condensing wall hung combination boilers
Hide thumbs Also See for GENUS HE SYSTEM 24:
Table of Contents

Advertisement

installation

Installing the Boiler

Please check that you are familiar with the installation
requirement before commencing work (pages 7 - 11).
The installation accessories described in the following list are
included in the boiler packaging:
- Hanging bracket
- A paper template (showing the dimensions of the boiler with
5 mm side clearances)
- Connection valves (compression)
- Screws and washers
- Filling loop
- Installation, Servicing and Operating Instructions
- Flue gasket
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct
positioning of kitchen cabinets etc.
The paper template has to be fixed to the wall and used to locate
the position of the hanging bracket and the centre for the flue
hole.
Drill and plug the wall and secure the hanging bracket using the
screws provided ensure the hanging bracket is level. Remove the
boiler from its packaging and remove the front casing panel.
Place the boiler on the hanging bracket.
N
: t
ote
he
appliaNce
must
Not
be
fitted
Connecting the Boiler to the System
- Remove the boiler casing as described on page 13;
- Remove the caps and connect the valves to the boiler using
the washers provided;
- 3 x fibre washers for the CH flow and return and cold water
inlet ;
Safety Valve Discharge and Condense Outlet
The pressure relief valve pipe is made of copper. It should
terminate below the boiler safely outside the premises. Care
should be taken that it does not terminate over an entrance or
window or where a discharge of heated water could endanger
occupants or passers by.
Warning !
Do not apply heat to the copper safety valve outlet pipe whilst
it is connected to the 3 bar safety relief valve.
Fill the central heating and DHW system and bleed air from the
system as described in the Commissioning instructions
(page 6).
The system should be carefully checked for leaks, as frequent
refilling could cause premature system corrosion or unnecessary
scaling of the heat exchanger. The pipe from the trap should be
connected to a drain as described in the relevant regulations.
Pay special attention not to bend the condensate silicone drain
pipe is such a way as to interrupt the flow. Please only use drain
pipe material compatible with condensate products (refer to BS
6798:000).
The condensate flow can reach  litres/hour because of the
acidity of the condensate products (Ph close to ), take care
before operation.
See page 11 for condensate discharge options.
1
Supplied By www.heating spares.co Tel. 0161 620 6677
.
oN
a
combustible
wall
surface
Note: Connections viewed from behind boiler
A
- remove the  screws A from the transport bar
- dispose of the transport bar and reassemble
the fixing screws.
A