TABLE OF CONTENTS GENERAL INFORMATION 1.1 G ENERAL NSTRUCTIONS 1.2 O VERALL INSTALLATION 2.1 R EFERENCE TANDARDS 2.2 S ITING THE PPLIANCE 2.3 O VERALL IMENSIONS 2.4 C LEARANCES 2.5 M OUNTING THE PPLIANCE 2.6 E LECTRICAL ONNECTION 2.7 G ONNECTION 2.8 W ATER...
This manual is an integral and essential part of the product. It should be kept GENERAL with the appliance so that it can be consulted by the user and our authorised INFORMATION personnel. Please carefully read the instructions and notices about the unit contained in this manual, as they provide important User’s Manual...
5 - If called for by point. 3, dismantling and cleaning of the combustion chamber. 6 - If called for by point. 4, dismantling and cleaning of the burner jets. 7 - Visual check of the primary heat exchanger: check for overheating in the blade assembly; clean the exhaust fan if needed.
This appliance is not suitable for outdoor installation. The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
VERALL IMENSIONS EGEND A = Central Heating Flow (3/4”) B = Domestic Hot Water Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold Water Inlet (1/2”) E = Central Heating Return (3/4”) LEARANCES In order to allow for access to the interior of the boiler for maintenance pur poses, the boiler must be installed in compliance with the minimum clearances indicated in F .
marked “L”. Note: The diagrams for the electrical system are indicated in section 2.11. Warning, this appliance must be earthed. External wiring to the appliance must be carried out by a qualified technician and be in accordance with the current I.E.E. Regulations and applicable local regulations.
Page 8
Copper tubing to BS EN 1057:1996 is recommended for water pipes. Jointing should be either with capillary soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air.
YSTEM ONNECTIONS The provision for satisfactory flue termination must be made as described in BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to.
Page 10
In addition, it is also possible to use a split (twin pipe) system by fitting a special adaptor to the flue connector and using the aperture for the air vent intake located on the top part of the combustion chamber. To utilise the air intake it is necessary to: 1.
Page 11
23 MFFI ABLE Exhaust Restrictor Restrictor Maximum Risk of Condensation Forming ø 41 mm ø 47 mm Extension Type Piping not insulated Piping insulated Exhaust/Air ø 41 ø 47 ø 41 ø 47 restrictor restrictor C12 (xx) Coaxial L min = 0.5 m L min = 2 m L = 4 m NONE...
In calculating the lengths of the pipes, the maximum length “L” must also take into consideration values YSTEMS exhaust/air intake end terminals, as well as 90° elbows for coaxial systems. The C52 types must comply with the following requirements: 1 - The exhaust/ air intake pipes must have the same diameter of 80 mm.
Page 13
2.12 LECTRICAL IAGRAM Circulation Pump EGEND Spark Generator/Gas Valve Supply = Time Clock Connector Motorised Diverter Valve = Central Heating Selection (Winter) and Flame Detection Circuit Temperature Adjustment Detection Electrode = Connector for Total Check System Main Circuit Temperature Probe = Domestic Hot Water Temperature Adjustment Domestic Hot Water Temperature Probe = Soft-light Adjustment...
COMMISSIONING MTS (GB) Limited support the initiative. Within the information pack NITIAL REPARATION you will find a copy of the logbook. It is important that this is completed in the presence of your customer, they are shown how to us it, and it is signed by them.
ONTROL ANEL EGEND A - On/Off knob B - Domestic hot water temperature adjustment knob C - Central heating selection (winter) and temperature adjustment knob D - On/Off L.E.D. (green) E - Fume sensor L.E.D. (yellow) F - Ignition failure (lockout) L.E.D. (red) G - “Economy/Comfort”...
HE CHECKS TO BE RUN BEFORE INITIAL START UP ARE AS FOLLOWS 3.4. I NITIAL TART 1. Make sure that: - the screw on the automatic air valve has been loosened when the system is full; - If the water pressure in the system is below 1 bar, bring it up to the appropriate level;...
readings can be The flue connector has two apertures, OMBUSTION NALYSIS taken for the temperature of the combustion by-products and of the combustion air, as well as of the concentrations of O and CO , etc. To access these intakes it is necessary to unscrew the front screw and remove the metal plate with sealing gasket.
5. A FROST DEVICE The boiler is equipped with a device that, in the event of the water temperature going below 5°C, the 3-way diverter valve switches to domestic hot water and the burner ignites at the minimum power until the boiler water reaches a temperature of about 50°C.
MAINTENANCE It is recommended that the following inspections be carried out on the boiler at least once a year: 1 - Check the seals for the water connections; replacement of any faulty seals. 2 - Check the gas seals; replacement of any faulty gas seals. 3 - Visual check of the entire unit.
MISCELLANEOUS IRING IAGRAM FOR EATING ONES BROWN BOILER ELECTRICAL SUPPLY CABLE BLUE GREY ORANGE Remove internal time clock plug from the the P.C.B. then connect GREEN/YELLOW TYPICAL room stat terminal block on the JUNCTION BOX V4043H reverse of the boiler control panel VALVE (see section 2.10) to 9 + 10 on •...
Page 23
IRING IAGRAM FOR ONNECTION TO AN RISTON NVENTED YLINDER BOILER ELECTRICAL SUPPLY CABLE Remove internal time clock plug T6360B from the the P.C.B. then connect TYPICAL ROOM room stat terminal block on the THERMOSTAT JUNCTION BOX reverse of the boiler control panel BROWN (see section 2.10) to 9 + 10 on •...
TECHNICAL INFORMATION 23 MFFI 27 MFFI CE Certification 63AU4549 63AU4549 Heat Input max/min kW 25.6/11.0 29.8/12.0 Heat Output max/min kW Efficiency of Nominal Heat Input 92.9 93.5 Efficiency at 30% of Nominal Heat Input 91.1 90.7 Heat Loss to the Casing (∆T=50°C) Flue Heat Loss with Burner Operating Flue Heat Loss with Burner Off Maximum Discharge of Fumes (G20)
Page 25
Servicing Instructions Type C Boilers G.C.N: 47-116-14 47-116-15 LEAVE THESE INSTRUCTIONS WITH THE END-USER Country of destination: GB...
Page 26
TABLE OF CONTENTS SERVICING INSTRUCTIONS EPLACEMENT OF ARTS ENERAL CCESS - Removing the front panel - Removing the sealed chamber frontal cover - Removing the side panels CCESS TO THE OMBUSTION HAMBER - Removing the combustion cover - Removing the burner and jets - Removing the electrodes - Removing the main heat exchanger - Removing the air pressure switch...
2. The control panel moves downward and when pulled forward, SERVICING INSTRUCTIONS rotates on two lateral hinges; the panel stays in a semi- horizontal position, which allows access to the inner parts of To ensure efficient safe operation, it is recommended that the the boiler (F .
Removing the sealed chamber frontal cover Removing the side panels 1. Remove the screws “C” (F . 1.6); 1. Remove the four screws “D” for each side panel (F .1.8); 2. Lift the sealed chamber frontal cover from the locating pins 2.
CCESS TO THE OMBUSTION HAMBER Removing the combustion cover 1. Remove the screws “E” (F . 1.10); 2. Lift off the combustion cover. Fig. 1.12 78 eps Removing the electrodes Before carrying out this procedure, unscrew and slide the burner forward (see previous section). 1.
3. Remove screw “H” (F . 1.15); Removing the main heat exchanger 4. Gently slide the electrode downward (F . 1.16). 1. Drain the boiler of water; 2. Release the overheat thermostat sensor “I” (F . 1.17); 3. Release the two connection nuts “J” connecting the exchanger to the flow and return pipes (F .
Removing the air pressure switch Removing the fan 1. Disconnect the electrical connections “K” and silicon pipes 1. Disconnect electrical connections “N” and silicon pipes “L” from their connection points (F . 1.20); “O” (F .1.23); 2. Remove screws “M” on the top of the sealed chamber 2.
ERVICING AND EMOVAL OF THE ALVE Setting the minimum and the maximum power of the boiler Setting the gas pressures 1. Check that the supply pressure to the gas valve is a minimum of 20 mbar for natural gas. 2. To do this, remove the screw “A”. Fit the pipe of the pressure gauge to the pressure connection of the gas valve “B”.
Page 33
Regulating the heating power for natural gas (G20) model 23 model 27 CG007A Regulating the heating power for butane gas (G30) model 23 model 27 CG008A Regulating the heating power for propane gas (G31) model 23 model 27 CG009A “A” ABLE 2.01 Kg/h 2.00 Kg/h...
Removing the gas valve CCESS TO THE ATER IRCUIT 1. Disconnect all the cables from the solenoid and Important! Before any component is removed, the boiler modureg; must be drained of all water. 2. Remove the spark generator (see previous section); 3.
Removing the safety valve Removing the main circuit flow switch 1. Loosen nut “Z” (F . 1.36); 2. Unscrew and remove the valve (F . 1.37). 1. Remove the cable of the main circuit flow switch “B1” . 1.40); 2. Remove the screws “C1” (F .
Removing the overheat thermostat Removing the D.H.W. temperature sensor (N.T.C.) 1. Disconnect overheat thermostat electrical 1. Pull off the electrical connector “Q1” and unscrew the connections “N1” (F . 1.54); sensor probe using a suitable spanner (F . 1.57). 2. Then remove the thermostat from its mounting by releasing the securing clip (F .
Removing the time clock CCESS TO THE ONTROL YSTEM 1. Unplug electrical connection “W1” from the clock (F Checking the fuses 1.62); 2. Remove the screws “W2” (see fig. 1.63); 1. Remove the inspection cover on the reverse of the 3.
Removing the P.C.B. 1. Isolate electricity; 2. Remove the inspection cover from the reverse of the control panel; 3. Unplug all electrical connections from the P.C.B. (F 1.65); 4. Remove the screws “X1” (F . 1.66); 5. Separate the facia panel from the rear of the control panel (F .
FAULT FINDING It is possible to detect and correct any defect by using the standard fault AULT INDING UIDE finding diagrams described in this chapter. CHARTS PRELIMARY CHECKS MAKE SURE THAT: 1 - There is sufficient water in the system 2 - The gas is turned on 3 - The electrical supply is turned on...
Page 43
IS THE PUMP RUNNING? POWER TO THE PUMP? DOES THE "NO WATER" L.E.D. ILLUMINATE 1 - Check pump cable (WITHIN 40 SECS)? 2 - Check/replace P.C.B. 1 - Check if there is air in the 3 - Check main flow main system switch operation when 2 - Check main circuit flow switch...
Page 44
IS THE FAN RUNNING? BOILER 1 - Reset the boiler SHUTDOWN? 1 - Check/replace main circuit flow switch PUMP PROTECTION 2 - Check/replace ACTIVATED? connection cable 3 - Check/replace P.C.B. 1 - Check/replace air INTERNAL pressure switch P.C.B. PROTECTION 2 - Check if reset button ACTIVATED? is jammed 3 - Check/replace flame...
Page 45
IS THE AIR PRESSURE SWITCH ACTIVATED? CHECK ∆ ∅ P 1.2 mbar 1 - Check A.P. switch cable ∆P ON TEST 2 - Check/replace A.P. switch PRESSURE 3 - Check/replace P.C.B. INTAKE ≤ ∆ 1 - Check exhaust discharge P 1.2 mbar 2 - Check venturi &...
Page 46
FAULTS POSSIBILE CAUSES Drawing D.H.W: THERE STILL - air in secondary heat exchanger When you turn on a tap A PROBLEM? - faulty main circuit flow switch burner switches off - faulty D.H.W. flow switch Drawing D.H.W: - faulty 3-way valve radiators heat up in summer mode Drawing D.H.W: - check C.H./D.H.W.
EGEND ELECTRICAL = Time Clock Connector DIAGRAMS = Central Heating Selection (Winter) and Temperature Adjustment = Connector for Total Check System = Domestic Hot Water Temperature Adjustment = Soft-light Adjustment = Maximum Heating Adjustment = On/Off Switch = On/Off L.E.D. = Fume Sensor L.E.D.
Page 54
Dear Customer, The guarantee on this appliance is valid for 24 months from the first Thank you for choosing an ARISTON day of installation. boiler. We guarantee that your boiler is a reliable Repairs to the electric, hydraulic and technically sound product.
Page 55
TABLE OF CONTENTS page 4 ENERAL NFORMATION Technical Information page 5 Control Panel page 6 page 8 PERATING NSTRUCTIONS SEFUL NFORMATION page 14 ROUBLESHOOTING page 16 AINTENANCE page 16 HANGE OF page 17 LOCK MPORTANT Please read this manual carefully. For additional information, please consult the “Installation and Servicing Instructions.”...
1. G use. ENERAL NFORMATION Do not allow children or inexperienced persons to use the appliance without MTS (GB) Limited support the supervision. initiative. Your installer will give you, and If you smell gas in the room, do not turn show you how to use, a logbook which will on light switches, use the telephone or give you important information about your...
Page 59
EGEND A - On/Off knob K - Central heating temperature B - Domestic hot water temperature L.E.D (yellow) adjustment knob L - Time clock C - Central heating selection M - Heating system pressure gauge (winter) and temperature adjustment knob D - On/Off L.E.D.
2. OPERATING INSTRUCTIONS ELPFUL UGGESTIONS AUTION To get the most out of your boiler, we nstallation, start-up, adjustments have provided you with some useful and maintenance must be performed advice proper by a competent person only, in maintenance: accordance with the current Gas - Periodically check system...
Page 61
value. Consult your installer for reducing gas consumption and checking and refilling the system. maintenance costs. - The outer panels of the unit's case - If the boiler should be out of use for must only be cleaned with a damp prolonged period, cloth.
Page 62
boiler fail to ignite a second time, check GNITION PROCEDURE that the external gas cock is open. If the Turn the selector knob “A” to the “J” problem persists, contact position. The green L.E.D. “D” will Authorised Service Centre. RESET UT011Aa UT011Aq illuminate indicating that the boiler is...
Page 63
the user can select winter or summer somewhere between min. and max., a operating mode. Keeping the knob “C” temperature may be obtained which at the “0” position selects the summer varies from approximately 45˚C to operating mode. Winter operating about 80˚C.
Page 64
it at max in order to temperature for the water may be obtain best chosen in a range from 36˚C to about performance from 56˚C, depending on the flow rate of the the boiler and to water and the position of the knob allow the regulation between the min.
Page 65
The comfort mode is a special URNING OFF THE BOILER operating state, because the water contained in the secondary exchanger To turn the boiler off, rotate the selector and in the primary exchanger is kept in knob “A” to the “0” position (OFF); the a preheated condition, thereby allowing respective green L.E.D.
L.E.D. “F” will illuminate. In order to 3. USEFUL INFORMATION reset the ignition, the button “H” must be pressed and released. Should the AND TROUBLESHOOTING boiler fail to ignite a second time, check that the external gas cock is open. If the OILER SHUTDOWN SITUATIONS problem persists,...
Page 67
within the system, have a plumber HUTDOWN DUE TO INSUFFICIENT check the heating system for possible WATER CIRCULATION water leaks. EMPORARY SHUTDOWN DUE TO If the red L.E.D. “L” is DEFECTIVE DISCHARGE OF illuminated boiler off, EXHAUST FUMES possible cause for this UT011Al state is an insufficient The boiler is fitted with safety devices,...
4. MAINTENANCE MPORTANT If this situation occurs frequently, contact an Authorised Service Centre. Schedule an annual maintenance so that they may check that the exhaust check-up boiler with fumes are being expelled correctly and competent person. that the area is ventilated properly. Correct maintenance always results in savings in the cost of running the FROST DEVICE...
inside (off setting) to the outside of the 6. TIME CLOCK clock border (on setting), the circuit is closed (switch on) for a period of 15 minutes and then the boiler starts if the room thermostat (if installed) or the heating thermostat require...
Page 70
clock border; on and will only shut off upon the - pull outward the riders for 7.00 am request of the room thermostat (if and 9.30 am, and then all riders installed) or the heating thermostat; between these two; - repeat this for 7.00 pm and 10.00 2.
Page 71
ECHNICAL Ambient temperature: - 10°C to + 55°C Running reserve: 150 h (not for 1.5 V DC) Shortest switching time: 15 minutes Programmable: Every 15 minutes...
Page 72
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiary: MTS (GB) LIMITED MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 Technical Service Hot Line: (01494) 539579...
Page 73
SPARE PARTS EXPLODED VIEW WALL-HUNG GAS BOILERS Models microGENUS 23 MFFI microGENUS 27 MFFI Edition 2 Current from Serial No:- 2320005600001to 2320021400002...