6.1 MODULE 1 - S
INPUT RANGE
rAN6E
SELECTION
RESOLUTION
0. 0 2A
200uA
0. 0 02A
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
DISPLAY DECIMAL POINT
dECPt
0
0. 0 00
Select the decimal point location for the Input, MIN and MAX displays. This
selection also affects the
and
dSP1
DISPLAY OFFSET VALUE
OFSEt
-19999
0. 0 00
The display can be corrected with an offset value. This can be used to
compensate for signal variations or sensor errors. This value is automatically
updated after a Zero Display to show how far the display is offset. A value of
zero will remove the effects of offset.
FILTER SETTING
FILtr
0,1 2 3
1
If the displayed value is difficult to read due to small process variations or
noise, increased levels of filtering will help to stabilize the display. Software
filtering effectively combines a fraction of the current input reading with a
fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1
for the filter uses 1/4 of the new input and 3/4 of the previous display to generate
the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A filter value
of 3 uses 1/16 new and 15/16 previous.
FILTER BAND
bANd
to
0
199
10
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the filter disengages. When the variation
becomes less than the band value, the filter engages again. This allows for a
stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of '0' keeps the filter permanently
engaged at the filter level selected above.
IGNAL

PARAMETER MENU

RANGE
RANGE
SELECTION
RESOLUTION
µ
200.00
A
20.000 mA
0. 0 2A
2.0000 mA
200.00 mA
0. 2 A
0. 0
0. 0 0
0. 0 00
parameters and setpoint values.
dSP2
to
19999
display units
I
P
NPUT
ARAMETERS
StYLE
KEy
If Input Values and corresponding Display Values are known, the Key-in
(
) scaling style can be used. This allows scaling without the presence or
KEY
changing of the input signal. If Input Values have to be derived from the actual
input signal source or simulator, the Apply (
INPUT VALUE FOR SCALING POINT 1
INP 1
0. 0 00
0. 0 000
For Key-in (
KEY
(The Input Range selection sets the decimal location for the Input Value).
For Apply (
APLY
retain this value, press the SEL button to advance to the next parameter. To
change the Input Value, press the RST button and apply the input signal to the
meter. Adjust the signal source externally until the desired Input Value appears.
Press the SEL button to enter the value being displayed.
DISPLAY VALUE FOR SCALING POINT 1
dSP 1
0. 0 00
Enter the first Display Value by using the front panel buttons. This is the same
for
and
KEY
APLY
INPUT VALUE FOR SCALING POINT 2
INP 2
10. 0 00
For Key-in (
KEY
panel buttons.
For Apply (
APLY
Scaling Point 2. To retain this value, press the SEL button to advance to the next
parameter. To change the Input Value, press the RST button and apply the input
signal to the meter. Adjust the signal source externally until the desired Input
Value appears. Press the SEL button to enter the value being displayed.
DISPLAY VALUE FOR SCALING POINT 2
dSP 2
10. 0 00
Enter the second Display Value by using the front panel buttons. This is the
same for
and
KEY
General Notes on Scaling
1. When using the Apply (
must be confined to the range limits shown.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 20 mA can not equal 0 and 20.)
3. For input levels beyond the programmed Input Values, the meter extends the
Display Value by calculating the slope from the two coordinate pairs (
&
/
dSP1
INP2
9
(
)
1-INP
SCALING STYLE
KEy
APLY
) scaling style must be used.
APLY
to
0
29999
) style, enter the first Input Value using the front panel buttons.
) style, the meter shows the previously stored Input Value. To
to
-19999
99999
scaling styles. The decimal point follows the
to
0
29999
) style, enter the known second Input Value using the front
) style, the meter shows the previously stored Input Value for
to
-19999
99999
scaling styles.
APLY
) scaling style, input values for scaling points
APLY
).
dSP2
selection.
dECPt
/
INP1