If the boiler does not give complete satisfaction,
before calling for a service engineer, the installer
should check the following:
General checks
1. Is there 230V across the boiler live and neutral terminals?
2. Is the polarity correct? (230V across live and earth, 0V across neutral and earth)
2. Is the air bled from the primary system?
3. Is the air bled from the oil supply?
4. If the flue sized and routed correctly?
Boiler runs straight to lockout
1. Has the oil line been purged of air.
2. Where an air eliminator is used in conjunction with a top feed oil tank
the non-return valve, (if fitted), should be removed from the oil dip pipe.
Boiler locks out at the start of a demand
(Heating off overnight for example)
1. If an air eliminator is being used, check that there are no leaks that allow
air to be pulled into the oil supply.
2. If a two pipe oil supply is a being used, has a non-return valve
been fitted to the inlet pipe? Refer to the instructions for guidelines.
No domestic hot water
1. Is the mains water in connected to the 15mm isolation valve?
2. Is there a domestic hot water demand from the programmer and has the
tank reached temperature?
No domestic hot water (external programmer)
1. Is there 230V on pin 2 of terminal block X4?
2. Remove the external wiring from terminal block X4 and fit a link across 1
and 2, if the domestic hot water now operates there is a problem with
the external programmer and/or its wiring.
No central heating
1. Are both programmer and room thermostat on demand for central heating?
2. Is the room thermostat wired correctly?
3. Refit the link across pins 2 and 3 on terminal X2, if the central heating
now operates correctly the room thermostat and/or its wiring are faulty.
No central heating (external programmer)
1. Are both programmer and room thermostat on demand for central heating?
2. Is the room thermostat wired correctly?
3. Refit the link across pins 2 and 3 on terminal X2, if the central heating
now operates correctly the room thermostat and/or its wiring are faulty.
4. Is there 230V on pin 1 of terminal block X4? If not remove the external wiring to
terminal block X4 and fit a link across pins 1 and 3 on terminal X4, if the central
heating now operates correctly the programmer and/or its wiring are faulty.
UNDER NO CIRCUMSTANCES MUST AN APPLIANCE BE LEFT
TO OPERATE WITH ANY CONTROL LINKED OUT OR OVER RIDDEN.
Dedicated to heating comfort
Worcester, Bosch Group
Cotswold Way, Warndon, Worcester WR4 9SW.
Tel. 0844 892 9900 Fax. 01905 754619
Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd.
www.worcester-bosch.co.uk
8 716 106 252f (03/2010)
Page 56
CONTACT INFORMATION
WORCESTER, BOSCH GROUP:
TECHNICAL:
0844 892 3366
SERVICE:
0844 892 3000
SERVICE (EIRE):
01494 0099
SPARES:
01905 752571
LITERATURE:
0844 892 9800
TRAINING:
01905 752526
SALES:
01905 752640
WEBSITE:
worcester-bosch.co.uk
WEBSITE (EIRE):
worcester-bosch.ie-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenstar heatslave 25/32Greenstar heatslave 18/25

Table of Contents