VENTING INSTALLATION
NOTE: Flex vent pipe spacers: Refer to manufacturer's
specifications for correct positioning of the
spacer springs to maintain proper distance
between inside and outside pipe.
Install the Ceiling Firestop
Frame an opening 9 in. x 9 in. (229 mm x 229 mm)
whenever the vent system penetrates a ceiling/floor .
Figure 55
Frame the area with the same sized lumber as used in
ceiling/floor joist.
When installing a top vent vertical termination appliance
the hole should be directly above the appliance, unless
the flue is offset.
The ceiling firestop may be installed above or below
the ceiling. Figure 56
Secure with three fasteners on each side.
Do not pack insulation around the pipe. Insulation must
be kept away from the pipe.
The gap between the vent pipe and firestop may be
sealed.
UL1777
Flex Vent
Figure 54 –
Minimum Radius for Flex Vent Section
FP1973
flex pipe bend
20306739
5" Radius
Figure 55 –
Installing Ceiling Firestop
Install attic insula-
tion shields before
or after installation
of vent system.
3 fasteners
Ceiling firestop
installed below ceiling.
Figure 56 –
Installing Ceiling Firestop & Attic Insulation Shield
CFDV Series Gas Fireplace
Attic Above
9 in. (229 mm)
9 in. (229 mm)
Hole should measure
9 in. x 9 in.
inside to inside
per side
Ceiling firestop
installed above ceiling.
29