Installation Sequence Siting And Levelling The Boiler; Changing The Boiler Door Opening; Connections On The Heating Water Side - Viessmann Vitoplex 100 PV1 Installation Instructions Manual

Oil/gas boiler
Hide thumbs Also See for Vitoplex 100 PV1:
Table of Contents

Advertisement

Siting and levelling the boiler
Fig. 3

Changing the boiler door opening

A
B
C
A
C
D
Fig. 4

Connections on the heating water side

Danger
Opening the connections on the heating water
side whilst the boiler is under pressure can
result in injuries.
First depressurise the boiler.
Note
Install all pipe connections free of load and torque
stress.
6
1.
B
Level the boiler horizontally. No special foundations
are required.
Note
We recommend siting the boiler on anti-vibration
boiler supports
(see chapter "Clearance dimen-
C
sions").
Anti-vibration boiler supports
Floor undulations must not be greater than 1 mm to
ensure that the spring elements are loaded evenly.
Position the boiler supports underneath the boiler by
placing them centrally under the base rails.
When setting the boiler down less than square on, a
boiler support can temporarily be overloaded. To aid
installation, support the boiler on 3 x timbers
(
35 mm).
Note
The boiler door is hung on the opposite side by moving
bolt
to the r.h. side. Sealing frame
A
centrally onto boiler door gasket
door is closed. If necessary, align mounting bracket
.
C
should press
B
when the boiler
D