Making The Safety Connection And Testing For Tightness - Viessmann Vitoplex 100 PV1 Installation Instructions Manual

Oil/gas boiler
Hide thumbs Also See for Vitoplex 100 PV1:
Table of Contents

Advertisement

Connections on the heating water side
D
C
B
A
E
Fig. 5
Boiler return
A
for 150 to 310 kW: DN 65
for 400 to 620 kW: DN 100
Safety connection (safety valve), see page 7
B
Boiler flow
C
for 150 to 310 kW: DN 65
for 400 to 620 kW: DN 100
Female connection for boiler water temperature
D
sensor, high limit safety cut-out and temperature
controller
Drain, R 1
E
¼

Making the safety connection and testing for tightness

Install the safety lines.
Safety connection
150 to 310 kW
400 to 620 kW
Permiss. operating pressure
Test pressure
Low water indicator
According to EN 12828, a low water indicator can be
omitted for Vitoplex 100 boilers up to 300 kW (except
in attic heating centres), as the standard boiler control
unit prevents impermissible heating.
If required, install a low water indicator or a minimum
pressure limiter into the pipework.
(cont.)
Note
Equip the boilers with a safety valve that is type-tested
according to EN 4126. The valve must be marked in
accordance with the system version.
R 1
¼
Install all pipe connections free of load and torque
R 1
½
stress.
!
5 bar (0.5 MPa)
6.5 bar (0.65 MPa)
Please note
Unsuitable water quality can damage the boiler
body.
Only fill the boiler with water that complies with
the "Water quality requirements" (see service
instructions).
7

Advertisement

Table of Contents
loading