Dc Rack Cabling - Nortel NN44200-300 Hardware Installation

Nortel networks server hardware installation instructions
Table of Contents

Advertisement

Length
0-210 m (700 ft)
Over 210 m (700 ft)
Notes:
1.
The cabinet and module ground wire specification is #10 AWG insulated green safety ground wire.
2.
The cabinet conduit can be 19.1 mm (0.75-in.) or 31.8 mm (1.25-in.), and must be insulated
from the cabinet ground.
Metric wire conversion
Industry standard
AWG No.
nominal (sq mm)
2
35
4
25
6
16
8
10
10
6
12
4
14
2.5
16
1.5
18
1
20
0.75
22
0.5

DC rack cabling

The following photograph shows typical rack power cabling:
Copyright © 2007, Nortel Networks
.
#10 AWG
#8 AWG
no
no
no
no
Nortel CallPilot
1002rp Server Hardware Installation
NN44200-300 01.01 Standard
5.0 23 February 2007
Junction
box #4
#6 AWG
AWG
no
no
no
no
Resistance at 20 C
(Ohm/100 m)
0.05
0.08
0.13
0.20
0.33
0.63
1.00
1.40
2.00
2.90
4.60
DC rack cabling 37
Junction
box #4
AWG
yes
no