Si06-313
2.5

Removal of the Sound Blanket

Procedure
before disassembling work.
Step
Disconnect the harness
1
of each thermistor.
Release the
discharge
2
pipe
thermistor.
3
Cut the clamp by
nippers.
Disconnect the
outdoor
heat exchanger
thermistor.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
Procedure
Outdoor Unit
Points
Pay attention to the direction
of the clip so as not to touch
the lead wire of the
thermistor when
reassembling.
Clamps should be always
available.
Fix it as it was before.
145