Power Transistor Check - Daikin B-Series Service Manual

Floor standing inverter pair
Hide thumbs Also See for B-Series:
Table of Contents

Advertisement

Si06-313
5.1.11
Capacitor Voltage Check
Check No.12
Before this checking, be sure to check the main circuit for short-circuit.
5.1.12

Power Transistor Check

Check No.13
Tester's negative terminal Power transistor
Tester's positive terminal
Normal resistance
Abnormal resistance
Service Diagnosis
Checking the capacitor voltage
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts.
Fan motor
lead wire
Solenoid valve
lead wire
Checking the power transistor
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
If unavoidably necessary to touch a live part, make sure the power transistor's supply
voltage is below 50 V using the tester.
For the UVW, make measurements at the Faston terminal on the board or the relay
connector.
Use the tester
in the DC range.
UVW
(+)
Power transistor
UVW
(+)
Several kohms to several Mohms
Compressor
lead wire
Reactor
lead wire
OL
lead wire
Thermistor
lead wire
(R2858)
Power transistor
(–)
Power transistor
UVW
0 or ∞
Check
UVW
(–)
111