Indoor Unit
Step
4
Dismount the six
screws (three for the
upper side motor and
three for the bottom
one) to remove the
motors.
Remove the motors
5
and
cross flow
fans.
6
To remove the casing,
dismount the four
screws at front side
and the other four
screws at rear side.
126
Procedure
fan
Si06-313
Points
Short lead wire: for the upper
fan motor
Long lead wire: for the
bottom fan motor
Mounting screw M4 × 16
Loosen the fixing screw to
separate the fan and motor.
Casing mounting screw
Front: M4 × 16
Rear: M4 × 14
Condition : Casing
Protruded : Not to be removed
Semi-sink : To be removed
Sink : Not to be removed
Removal Procedure