5.12 Electrical connection of the re-
mote control (optional)
Use the terminals indicated in (Figure 5.23) to
connect the remote control.
The installation of the remote control ex-
cludes the installation of the remote control.
To connect the remote control to the boiler, re-
fer also to the REMOTE CONTROL manual.
The electric jumper between "A and B" must
be removed (Figure 5.23).
5.13 Remote enabling of operation
with the external probe
Functioning with the external probe in the
boiler must be enabled if the remote control is
used.
The programming of the REMOTE (if installed)
is used to enable its operation.
• Press the button
to enter
mode.
0
21
3
1
8
6
9
1 5
1
2
Figure 5.24
Press buttons
and
transparent programming (Figure 5.25).
- 44 -
INSTALLATION
for more than 3 seconds
together to enter
Figure 5.25
• Press buttons
"PM15" program that enables the external
probe (Figure 5.26).
Figure 5.26
• Modify the programmed SET by pushing
until a setting of 60 is dis-
or
played and wait for the programmed number
to flash (Figure 5.27).
Figure 5.27
• Press to exit programming.
or
to display the