Installing The External Unit; Installation Information; Installation Site - Viessmann VITOCAL 200-S Installation And Service Instructions Manual

Table of Contents

Advertisement

Installation sequence

Installing the external unit

Installation information

Types of installation:
Floorstanding installation with line entry above
ground level
Floorstanding installation with line entry below
ground level
Wall mounting
Technical guide
Floorstanding installation:
Use supports for floorstanding installation (accesso-
ries).
Where such supports cannot be used, install the
external unit freestanding on a solid base of
at least 100 mm height.
In difficult climatic circumstances (temperatures
below zero, snow, humidity) install the appliance on
a plinth of approx. 300 mm height.
Take into account the weight of the external unit: See
the following table.
Wall mounting:
Use the wall mounting bracket set (accessories).
The wall must meet the structural requirements.
Positioning:
Never install with the discharge side facing the main
wind direction.
Provide wall ducts and protective pipes for the refrig-
erant lines and electrical cables without moulded
parts and change of direction.
Weather influences:
Observe wind loads when installing the unit on sites
exposed to the wind.
Incorporate the external unit into the lightning protec-
tion system.
Consider the heat emitted by the unit when planning
your weatherproofing or an enclosure.

Installation site

Select a site with good air circulation, so that the
cooled air can dissipate and be replaced by warm
air.
Avoid direct insolation.
When siting the unit where it is exposed to wind,
ensure that the wind cannot influence the fan area.
Strong wind can have a negative influence on the
evaporator ventilation.
Take into account the lengths of the refrigerant lines:
See "Connecting refrigerant lines".
Select the installation site so that the evaporator can-
not be blocked by leaves, snow etc.
8
Condensate:
Ensure the condensate can drain freely, and create a
permanent gravel bed below the external unit as a
soakaway.
In regions with prolonged cold seasons (such as
Sweden for example), provide an electric ribbon
heater (accessory) for the condensate pan.
Insulation against structure-borne noise and vibra-
tions between building and external unit:
When line entry is above ground level, fit pipe bends
in the refrigerant lines for vibration compensation:
See "Connecting refrigerant lines".
Route electrical cables/leads between the internal
and external units free of stress.
Installation only on walls with high weight per area (
2
250 kg/m
), in other words not on lightweight walls,
roof structures etc.
For floorstanding installation, only use the rubber
mounts supplied.
For wall mounting, only use the anti-vibration mounts
from the bracket set.
Never use additional anti-vibration mounts, springs,
rubber mounts, etc.
Weight of external units
Type
AWB/AWB-AC
201.B04
201.B07
201.B10
201.B13
201.C10
201.C13
Select the installation site giving due consideration to
the physical laws concerning the propagation and
reflection of sound.
Technical guide "Heat pump principles"
>
Weight in kg
43
66
113
113
113
113