Gas Hook-Up Instructions
EN

Natural Gas Hook-Up

The gas appliance is designed to operate with natural gas at an inlet pressure of 7 inches water column.
The piping up to the appliance is the responsibility of the installer. A flexible metal connector is included
to simplify the installation of the appliance. Ensure that the connector does not pass through a wall, floor,
ceiling or partition, and is protected from damage. Do not use a hose to connect the appliance. The gas
supply pipe must be sufficiently sized to supply the BTU/h specified on the rating plate, based on the
length of the piping run.
Purge the gas supply line of any trapped air prior to the first firing of the appliance.
WARNING!
www.napoleongrills.com

GAS CONNECTION

Risk of fire, explosion or asphyxiation, ensure there are no ignition sources such as sparks or open
flames.
The installation must be performed by a licensed gas fitter, and all connections must be leak tested
before operating the appliance.
All gas connections must be contained within the appliance when complete.
High pressure will damage the valve, disconnect gas supply piping before testing gas line at test
pressures above 1/2 psig.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54 in the United States
Leak test all the connections by brushing on a soap and water solution. These connections can be
accessed by removing the burner. (See burner removal instructions.)