6-30. Increasing the Fan Speed
If external static pressure is too great (due to long
extension of ducts, for example), the air flow volume
may drop too low at each air outlet. This problem may
be solved by increasing the fan speed using the
following procedure:
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets
between the disconnected fan motor sockets in
step 2 as shown in the Fig. 1-114.
(5) Place the cable neatly in the box and reinstall the
cover plate.
How to read the diagram
The vertical axis is the external static pressure
(Pa) while the horizontal axis represents the air
flow (CFM).
The characteristic curves for "HT", "H", "M" and "L"
fan speed control are shown.
The nameplate values are shown based on the
"H" air flow. For the Type 26, the air flow is 636
CFM, while the external static pressure is 49 Pa
at "H" position. If external static pressure is too
great (due to long extension of duct, for example),
the air flow volume may drop too low at each air
outlet.
This problem may be solved by increasing the fan
speed as explained above.
Refer to "
SUPPLEMENT ON DRAIN PIPING".
Electrical component box
Booster cable
Fan
motor
Fan motor socket
(At shipment)
Indoor Fan Performance
Type 26
150
0.5
100
0.4
0.3
HT
50
0.2
H
0.1
M
L
0
0
300
500
700
900
Air Flow (CFM)
HT : Using the booster cable
NOTE
H : At shipment
1-145
1. Specifications
Booster cable
(Booster cable installed)
Fig. 1-114
Type 36
200
150
100
50
M
L
0
500
1000
Air Flow (CFM)
Fig. 1-115
1
0.8
0.6
0.5
0.4
0.3
HT
0.2
H
0.1
0