Flue System - Biasi Advance Plus 25C ERP User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for Advance Plus 25C ERP:
Table of Contents

Advertisement

touched by a person using the bath or
shower.
The location must permit the provision of an
adequate flue and termination.
For unusual locations special procedures
may be necessary and BS 6798 gives de-
tailed guidance on this aspect.
A compartment used to enclose the appli-
ance must be designed specifically for this
purpose. This appliance is not suitable for
external installation.
5.3

Flue system

The provision for satisfactory flue termina-
tion must be made as described in BS 5440
part 1.
For Ireland (IE), refer to I.S.813.2002.
The appliance must be installed so that the
flue terminal is exposed to external air.
It must not be installed so that the terminal
discharges into an other room or space as
an outhouse or lean-to. It is important that
the position of the terminal allows a free
passage of air across at all times.
The terminal should be located with due
regard for the damage or discoloration that
might occur to building products in the vicin-
ity.
In cold and/or humid weather water vapour
may condense on leaving the flue terminal;
the effect of such "steaming" must be con-
sidered.
Pluming may easily occur at the terminal.
Where possible, terminal position which
could cause a nuisance should be avoided.
The minimum acceptable spacing from
the terminal to obstructions and ventilation
openings are specified in Fig. 5.1.
GENERAL REQUIREMENTS
BC
G
E
L
JK
I
Fig. 5.1
Terminal position
A Directly below the window or
other opening
B Below gutters, soil pipes or drain
pipes
C Below eaves
D Below balconies*
E Below car port roof
F From vertical drain pipes and
soil pipes
G From internal corners**
H From external corners
I
Above ground or balcony level***
J From a wall or surface
K From a terminal facing a terminal 2500
L From an opening in the car port
(e.g. door, window) into dwelling
M Vertically from a terminal in the
same wall
N Horizontally from a terminal in
the same wall
O Above the roof pitch with roof
slope less than or equal to 30°
O Above the roof pitch with roof
slope more than 30°
P From wall face
Q From, above or to side of an
opening
* Wherever practicable to do so, the flue
O
H
P
I
F
A
D
Q
I
M
N
I
I
mm
300
75
200
600
NO
150
450
300
300
600
NO
1500
300
350
600
600
600
- 39 -
- 39 -